26-60 Terminal X42/11 Output
Option:
Function:
[109] Max Out Freq
[113] Ext. Closed Loop 1
0-100%, (0-20 mA)
[114] Ext. Closed Loop 2
0-100%, (0-20 mA)
[115] Ext. Closed Loop 3
0-100%, (0-20 mA)
[139] Bus ctrl.
0-100%, (0-20 mA)
[141] Bus ctrl t.o.
0-100%, (0-20 mA)
26-61 Terminal X42/11 Min. Scale
Range:
Function:
0 %
*
[0 - 200
%]
Scale the minimum output of the selected
analog signal at terminal X42/11, as a
percentage of the maximum signal level. E.g. if
a 0 V is desired at 25% of the maximum output
value. Then programme 25%. Scaling values up
to 100% can never be higher than the
corresponding setting in
.
See principle graph for
6-51 Terminal 42 Output Min Scale
26-62 Terminal X42/11 Max. Scale
Range:
Function:
100
%
*
[0 -
200
%]
Scale the maximum output of the selected analog
signal at terminal X42/9. Set the value to the
maximum value of the voltage signal output. Scale
the output to give a voltage lower than 10 V at full
scale; or 10 V at an output below 100% of the
maximum signal value. If 10 V is the desired output
current at a value between 0-100% of the full-scale
output, programme the percentage value in the
parameter, i.e. 50% = 10 V. If a voltage between 0
and 10 V is desired at maximum output, calculate
the percentage as follows:
(
10
V
desired maximum voltage
)
x100 %
i.e.
5
V : 10V
5
V x100 % = 200 %
See principle graph for
6-52 Terminal 42 Output Max Scale
26-63 Terminal X42/11 Bus Control
Range:
Function:
0 %
*
[0 - 100 %] Holds the level of terminal X42/11 if
controlled by bus.
26-64 Terminal X42/11 Timeout Preset
Range:
Function:
0 %
*
[0 - 100 %] Holds the preset level of terminal X42/11.
In case a bus time-out and a time-out
function are selected, the output will preset
to this level.
Parameter Description
VLT
®
Refrigeration Drive Programming Guide
MG16H102 - VLT
®
is a registered Danfoss trademark
163