13-01 Start Event
Option:
Function:
[21] Alarm (trip lock)
See parameter group 5-3* for further
description.
[22] Comparator 0
Use the result of comtor 0 in the logic
rule.
[23] Comparator 1
Use the result of comtor 1 in the logic
rule.
[24] Comparator 2
Use the result of comtor 2 in the logic
rule.
[25] Comparator 3
Use the result of comtor 3 in the logic
rule.
[26] Logic rule 0
Use the result of logic rule 0 in the
logic rule.
[27] Logic rule 1
Use the result of logic rule 1 in the
logic rule.
[28] Logic rule 2
Use the result of logic rule 2 in the
logic rule.
[29] Logic rule 3
Use the result of logic rule 3 in the
logic rule.
[33] Digital input DI18
Use the value of DI18 in the logic rule
(High = TRUE).
[34] Digital input DI19
Use the value of DI19 in the logic rule
(High = TRUE).
[35] Digital input DI27
Use the value of DI27 in the logic rule
(High = TRUE).
[36] Digital input DI29
Use the value of DI29 in the logic rule
(High = TRUE).
[37] Digital input DI32
Use the value of DI32 in the logic rule
(High = TRUE).
[38] Digital input DI33
Use the value of DI33 in the logic rule
(High = TRUE).
[39] Start command
This event is TRUE if the frequency
converter is started by any means
(either via digital input, field bus or
other).
[40] Drive stopped
This event is TRUE if the frequency
converter is stopped or coasted by any
means (either via digital input, fieldbus
or other).
[41] Reset Trip
This event is TRUE if the frequency
converter is tripped (but not trip-
locked) and [Reset] is pressed.
[42] Auto Reset Trip
This event is TRUE if the frequency
converter is tripped (but not trip-
locked) and an Automatic Reset is
issued.
[43] OK Key
This event is TRUE if [OK] is pressed.
[44] Reset Key
This event is TRUE if [Reset] is pressed.
13-01 Start Event
Option:
Function:
[45] Left Key
This event is TRUE if [
◄
] is pressed.
[46] Right Key
This event is TRUE if [
►
] is pressed.
[47] Up Key
This event is TRUE if [
▲
] is pressed.
[48] Down Key
This event is TRUE if [
▼
] is pressed.
[50] Comparator 4
Use the result of comtor 4 in the logic
rule.
[51] Comparator 5
Use the result of comtor 5 in the logic
rule.
[60] Logic rule 4
Use the result of logic rule 4 in the
logic rule.
[61] Logic rule 5
Use the result of logic rule 5 in the
logic rule.
13-02 Stop Event
Option:
Function:
Select the boolean (TRUE or FALSE)
input to deactivate Smart Logic
Control.
[0]
*
False
Enters the fixed value of FALSE in the
logic rule.
[1]
True
Enters the fixed value TRUE in the
logic rule.
[2]
Running
See parameter group 5-3* for further
description.
[3]
In range
See parameter group 5-3* for further
description.
[4]
On reference
See parameter group 5-3* for further
description.
[5]
Torque limit
See parameter group 5-3* for further
description.
[6]
Current Limit
See parameter group 5-3* for further
description.
[7]
Out of current
range
See parameter group 5-3* for further
description.
[8]
Below I low
See parameter group 5-3* for further
description.
[9]
Above I high
See parameter group 5-3* for further
description.
[10] Out of speed range
[11] Below speed low
See parameter group 5-3* for further
description.
[12] Above speed high
See parameter group 5-3* for further
description.
[13] Out of feedb.
range
See parameter group 5-3* for further
description.
Parameter Description
VLT
®
Refrigeration Drive Programming Guide
MG16H102 - VLT
®
is a registered Danfoss trademark