23-11 Maintenance Action
Array [20]
Option:
Function:
Select the action to be associated with
the Preventive Maintenance Event.
[1]
Lubricate
[2]
Clean
[3]
Replace
[4]
Inspect/Check
[5]
Overhaul
[6]
Renew
[7]
Check
[20] Maintenance Text 0
[21] Maintenance Text 1
[22] Maintenance Text 2
[23] Maintenance Text 3
[24] Maintenance Text 4
[25] Maintenance Text 5
23-12 Maintenance Time Base
Array [20]
Option:
Function:
Select the time base to be associated with the
Preventive Maintenance Event.
[0] Disabled
[0] Disabled
must be used when disabling the
Preventive Maintenance Event.
[1] Running
Hours
[1] Running Hours
is the number of hours the
motor has been running. Running hours are
not reset at power-on. The
Maintenance Time
Interval
must be specified in
23-13 Maintenance Time Interval
.
[2] Operating
Hours
[2] Operating Hours
is the number of hours the
frequency converter has been running.
Operating hours are not reset at power-on.
The
Maintenance Time Interval
must be
specified in
23-13 Maintenance Time Interval
[3] Date & Time
[3] Date & Time
uses the internal clock. The
date and time of the next maintenance
occurrence must be specified in
23-14 Maintenance Date and Time
.
23-13 Maintenance Time Interval
Array [20]
Range:
Function:
1 h
*
[1 -
2147483647
h]
Set the interval associated with the current
Preventive Maintenance Event. This
parameter is only used if
[1] Running Hours
or
[2] Operating Hours
is selected in
. The timer is
reset from
.
Example:
23-13 Maintenance Time Interval
Array [20]
Range:
Function:
A Preventive Maintenance Event is set up
Monday at 8:00.
is
[2] Operating hours
and
23-13 Maintenance Time Interval
is 7 x 24
hours=168 hours. Next Maintenance Event
will be indicated the following Monday at
8:00. If this Maintenance Event is not reset
until Tuesday at 9:00, the next occurrence
will be the following Tuesday at 9:00.
23-14 Maintenance Date and Time
Array [20]
Range:
Function:
Size
related
*
[ 0 -
0 ]
Set the date and time for next maintenance
occurrence if the Preventive Maintenance
Event is based on date/time. Date format
depends on the setting in
while the time format depends on the
setting in
NOTE
The frequency converter has no back up
of the clock function and the set date/
time will reset to default (2000-01-01
00:00) after a power down. In
it is possible to program for a
Warning in case the clock has not been
set properly, e.g. after a power down.
The time set must be at least one hour
from the actual time!
NOTE
When mounting an Analog I/O MCB 109
option card, a battery back up of the
date and time is included.
3.18.4 23-1* Maintenance Reset
23-15 Reset Maintenance Word
Option:
Function:
Set this parameter to
[1] Do reset
to reset the
Maintenance Word in
and reset the message displayed in the LCP.
This parameter will change back to
[0] Do not
reset
when pressing [OK].
[0]
*
Do not
reset
[1]
Do reset
Parameter Description