5-13 Terminal 29 Digital Input
Option:
Function:
Select the function from the available digital
input range and the additional options [60],
[61], [63] and [64]. Counters are used in
Smart Logic Control functions.
[0]
*
No operation Functions are described under parameter
group 5-1*
5-14 Terminal 32 Digital Input
Option:
Function:
Select the function from the available
digital input range and the additional
options [60], [61], [63] and [64]. Counters
are used in Smart Logic Control functions.
[39]
*
Day/Night
control
Functions are described under parameter
group 5-1*
5-15 Terminal 33 Digital Input
Option:
Function:
Select the function from the available digital
input range and the additional options [60],
[61], [63] and [64]. Counters are used in
Smart Logic Control functions.
[0]
*
No operation Functions are described under parameter
group 5-1*
5-16 Terminal X30/2 Digital Input
Option:
Function:
[0]
*
No operation This parameter is active when option module
MCB101 is installed in the frequency
converter. Functions are described under
parameter group 5-1*
5-17 Terminal X30/3 Digital Input
Option:
Function:
[0]
*
No operation This parameter is active when option module
MCB101 is installed in the frequency
converter. Functions are described under
parameter group 5-1*
5-18 Terminal X30/4 Digital Input
Option:
Function:
[0]
*
No operation This parameter is active when option module
MCB101 is installed in the frequency
converter. Functions are described under
parameter group 5-1*
5-19 Terminal 37 Safe Stop
Option:
Function:
[1]
*
Safe Stop
Alarm
Coasts frequency converter when safe
stop is activated. Manual reset from LCP,
digital input or fieldbus.
[3]
Safe Stop
Warning
Coasts frequency converter when safe
stop is activated (T-37 off). When safe
stop circuit is reestablished, the frequency
5-19 Terminal 37 Safe Stop
Option:
Function:
converter will continue without manual
reset.
Choises 4 - 9 are only available when the MCB 112 PTC
Thermistor Card is connected.
NOTE
When Auto Reset/Warning is selected the frequency
converter opens up for automatic restart.
Overview of functions, alarms and warnings
Function
No.
PTC
Relay
No Function
[0]
-
-
Safe Stop Alarm
[1]*
-
Safe Stop [A68]
Safe Stop Warning
[3]
-
Safe Stop [W68]
PTC 1 Alarm
[4]
PTC 1 Safe Stop
[A71]
-
PTC 1 Warning
[5]
PTC 1 Safe Stop
[W71]
-
PTC 1 & Relay A
[6]
PTC 1 Safe Stop
[A71]
Safe Stop [A68]
PTC 1 & Relay W
[7]
PTC 1 Safe Stop
[W71]
Safe Stop [W68]
PTC 1 & Relay A/W [8]
PTC 1 Safe Stop
[A71]
Safe Stop [W68]
PTC 1 & Relay W/A [9]
PTC 1 Safe Stop
[W71]
Safe Stop [A68]
Table 3.12
W means warning and A means alarm. For further information, see
Alarms and Warnings in section Troubleshooting in the Design Guide
or the Operating Instructions
A dangerous failure related to Safe Stop will give Alarm:
Dangerous Failure [A72].
Refer to
in .
3.7.3 5-3* Digital Outputs
Parameters for configuring the output functions for the
output terminals. The 2 solid-state digital outputs are
common for terminals 27 and 29. Set the I/O function for
terminal 27 in
, and set the I/O
function for terminal 29 in
. These
parameters cannot be adjusted while the motor is running.
The digital outputs can be programmed
with these functions:
[0]
No operation
Default for all digital outputs and relay
outputs
[1]
Control ready
The control board receives supply voltage.
Parameter Description