[74]
Logic Rule 4
See parameter group 13-4*. If Logic Rule 4
is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[75]
Logic Rule 5
See parameter group 13-4*. If Logic Rule 5
is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[80]
SL Digital
Output A
See
13-52 SL Controller Action
. The input
will go high whenever the Smart Logic
Action
[38] Set digital out. A high
is
executed. The input will go low whenever
the Smart Logic Action
[32] Set digital out.
A low
is executed.
[81]
SL Digital
Output B
See
13-52 SL Controller Action
. The input
will go high whenever the Smart Logic
Action
[39] Set digital out. B high
is
executed. The input will go low whenever
the Smart Logic Action
[33] Set digital out.
B low
is executed.
[82]
SL Digital
Output C
See
13-52 SL Controller Action
. The input
will go high whenever the Smart Logic
Action
[40] Set digital out. C high
is
executed. The input will go low whenever
the Smart Logic Action
[34] Set dig. out. C
low
is executed.
[83]
SL Digital
Output D
See
13-52 SL Controller Action
. The input
will go high whenever the Smart Logic
Action
[41] Set digital out. D
high is
executed. The input will go low whenever
the Smart Logic Action
[35] Set digital out.
D low
is executed.
[84]
SL Digital
Output E
See
13-52 SL Controller Action
. The input
will go high whenever the Smart Logic
Action
[42] Set digital out. E high
is
executed. The input will go low whenever
the Smart Logic Action
[36] Set digital out.
E low
is executed.
[85]
SL Digital
Output F
See
13-52 SL Controller Action
. The input
will go high whenever the Smart Logic
Action
[43] Set digital out. F high
is
executed. The input will go low whenever
the Smart Logic Action
[37] Set digital out.
F low
is executed.
[160] No alarm
The output is high when no alarm is
present.
[161] Running
reverse
The output is high when the frequency
converter is running counter clockwise
(the logical product of the status bits
‘running’ AND ‘reverse’).
[165] Local reference
active
The output is high when
=
[2] Local
or when
=
[0] Linked to Hand/Auto
at the same
time as the LCP is in Hand on mode.
[166] Remote
reference
active
The output is high when
=
[1] Remote
or
[0] Linked to Hand/
Auto
while the LCP is in [Auto On] mode.
[167] Start
command
active
The output is high when there is an active
Start command (i.e. via digital input bus
connection or [Hand On] or [Auto On],
and no Stop or Start command is active.
[168] Drive in hand
mode
The output is high when the frequency
converter is in Hand on mode (as
indicated by the LED light above [Hand
On].
[169] Drive in auto
mode
The output is high when the frequency
converter is in Hand on mode (as
indicated by the LED light above [Auto
On].
[180] Clock Fault
The clock function has been reset to
default (2000-01-01) because of a power
failure.
[181] Preventive
Maintenance
One or more of the Preventive
Maintenance Events programmed in
, has passed the
time for the specified action in
[190] No-Flow
A No-Flow situation or Minimum Speed
situation has been detected if enabled in
and/or
[191] Dry Pump
A Dry Pump condition has been detected.
This function must be enabled in
[192] End of Curve
A pump running with max. speed for a
period of time without reaching the set
pressure has been detected. To enable
this function, see
[193] Sleep Mode
The frequency converter/system has
turned into sleep mode. See parameter
group 22-4*
Sleep Mode
.
[194] Broken Belt
A Broken Belt condition has been
detected. This function must be enabled
in
[195] Bypass Valve
Control
The bypass valve control (Digital / Relay
output in the frequency converter) is used
for compressor systems to unload the
compressor during start-up by using a
bypass valve. After the start command is
given the bypass valve will be open until
the frequency converter reaches
4-11 Motor Speed Low Limit [RPM]
). After
the limit has been reached the bypass
valve will be closed, allowing the
compressor to operate normally. This
procedure will not be activated again
before a new start is initiated and the
frequency converter speed is zero during
the receiving of start signal.
1-71 Start
Delay
can be used in order to delay the
motor start. The Bypass valve control
principle:
Parameter Description
VLT
®
Refrigeration Drive Programming Guide
MG16H102 - VLT
®
is a registered Danfoss trademark
65