3.7 Main Menu - Digital In/Out - Group 5
Parameter group for configuring the digital input and
output.
3.7.1 5-0* Digital I/O Mode
Parameters for configuring the input and output using
NPN and PNP.
5-00 Digital I/O Mode
Option:
Function:
Digital inputs and programmed digital
outputs are pre-programmable for
operation either in PNP or NPN systems.
[0]
*
PNP - Active
at 24V
Action on positive directional pulses (0).
PNP systems are pulled down to GND.
[1]
NPN - Active
at 0V
Action on negative directional pulses (1).
NPN systems are pulled up to +24 V,
internally in the frequency converter.
NOTE
This parameter cannot be changed while the motor is
running.
5-01 Terminal 27 Mode
Option:
Function:
[0]
*
Input
Defines terminal 27 as a digital input.
5-01 Terminal 27 Mode
Option:
Function:
[1]
Output
Defines terminal 27 as a digital output.
NOTE
This parameter cannot be changed while the motor is
running.
5-02 Terminal 29 Mode
Option:
Function:
[0]
*
Input
Defines terminal 29 as a digital input.
[1]
Output
Defines terminal 29 as a digital output.
NOTE
This parameter cannot be changed while the motor is
running.
3.7.2 5-1* Digital Inputs
Parameters for configuring the input functions for the
input terminals.
The digital inputs are used for selecting various functions
in the frequency converter. All digital inputs can be set to
the following functions:
Digital input function
Select
Terminal
No operation
[0]
All *term 32, 33
Reset
[1]
All
Coast inverse
[2]
All
Coast and reset inverse
[3]
All
DC-brake inverse
[5]
All
Stop inverse
[6]
All
External interlock
[7]
All
Start
[8]
All *term 18
Latched start
[9]
All
Reversing
[10]
All *term 19
Start reversing
[11]
All
Jog
[14]
All *term 29
Preset reference on
[15]
All
Preset ref bit 0
[16]
All
Preset ref bit 1
[17]
All
Preset ref bit 2
[18]
All
Freeze reference
[19]
All
Freeze output
[20]
All
Speed up
[21]
All
Speed down
[22]
All
Set-up select bit 0
[23]
All
Set-up select bit 1
[24]
All
Ramp bit 0
[34]
All
Mains failure inverse
[36]
All
Parameter Description
VLT
®
Refrigeration Drive Programming Guide
MG16H102 - VLT
®
is a registered Danfoss trademark
59