5-54 Pulse Filter Time Constant #29
Range:
Function:
100
ms
*
[1 - 1000
ms]
Enter the pulse filter time constant. The
pulse filter dampens oscillations of the
feedback signal, which is an advantage if
there is a lot of noise in the system. A high
time constant value results in better
dampening but also increases the time
delay through the filter.
NOTE
This meter cannot be adjusted while
the motor is running.
5-55 Term. 33 Low Frequency
Range:
Function:
100 Hz
*
[0 - 110000
Hz]
Enter the low frequency
corresponding to the low motor shaft
speed (i.e. low reference value) in
5-57 Term. 33 Low Ref./Feedb. Value
.
5-56 Term. 33 High Frequency
Range:
Function:
100 Hz
*
[0 - 110000
Hz]
Enter the high frequency
corresponding to the high motor shaft
speed (i.e. high reference value) in
5-58 Term. 33 High Ref./Feedb. Value
.
5-57 Term. 33 Low Ref./Feedb. Value
Range:
Function:
0
*
[-999999.999 -
999999.999 ]
Enter the low reference value [RPM]
for the motor shaft speed. This is also
the low feedback value, see also
5-52 Term. 29 Low Ref./Feedb. Value
5-58 Term. 33 High Ref./Feedb. Value
Range:
Function:
100
*
[-999999.999 -
999999.999 ]
Enter the high reference value
[RPM] for the motor shaft speed.
See also
5-59 Pulse Filter Time Constant #33
Range:
Function:
100 ms
*
[1 - 1000
ms]
Enter the pulse filter time constant. The
low-pass filter reduces the influence on
and dampens oscillations on the feedback
signal from the control.
This is an advantage, e.g. if there is a
great amount on noise in the system.
NOTE
This parameter cannot be adjusted while the motor is
running.
3.7.6 5-6* Pulse Outputs
Parameters for configuring the scaling and output
functions of pulse outputs. The pulse outputs are
designated to terminals 27 or 29. Select terminal 27 output
in
and terminal 29 output in
Output value
Output
(Hz)
High output
value
P 5-60(term27)
P 5-63(term29)
High freq.
P 5-62(term27)
P 5-65(term29)
130BA089.11
Illustration 3.25
Select the operation variable assigned for terminal 27
readouts.
This meter cannot be adjusted while the motor is running.
Same options and functions as parameter group 5-6*.
[0]
*
No operation
5-62 Pulse Output Max Freq #27
Range:
Function:
Set the maximum frequency for
terminal 27, corresponding to the
output variable selected in
5-60 Terminal 27 Pulse Output Variable
.
NOTE
This meter cannot be adjusted
while the motor is running.
5000 Hz
*
[0 - 32000
Hz]
NOTE
This meter cannot be adjusted while the motor is running.
5-63 Terminal 29 Pulse Output Variable
Select the variable for viewing on the terminal 29 display. Same
options and functions as parameter group 5-6*.
Option:
Function:
[0]
*
No operation
[45]
Bus ctrl.
[48]
Bus ctrl., timeout
Parameter Description
VLT
®
Refrigeration Drive Programming Guide
MG16H102 - VLT
®
is a registered Danfoss trademark
69