Selected
Event
Relay
output
Selected
Event
Relay
output
On Delay
P 5-41
On Delay
P 5-41
Off Delay
P 5-42
130BA171.10
Illustration 3.22
5-42 Off Delay, Relay
Array[2]: Relay1[0], Relay2[1]
Range:
Function:
0.01 s
*
[0.01 - 600 s] Enter the delay of the relay cut-out time.
Select one of available mechanical relays
and MCB 105 in an array function. See
Selected
Event
Relay
output
On Delay
P 5-41
Off Delay
P 5-42
130BA172.10
Illustration 3.23
If the selected Event condition changes before the on- or
off delay timer expires, the relay output is unaffected.
3.7.5 5-5* Pulse Input
The pulse input parameters are used to define an
appropriate window for the impulse reference area by
configuring the scaling and filter settings for the pulse
inputs. Input terminals 29 or 33 act as frequency reference
inputs. Set terminal 29 (
5-13 Terminal 29 Digital Input
) or
terminal 33 (
5-15 Terminal 33 Digital Input
) to
[32] Pulse
input
. If terminal 29 is used as an input, then set
to
[0] Input
.
130BA076.10
(RPM)
Ref.
Low freq.
P 5-50/
P 5-55
Input
(Hz)
High
ref.
value
P 5-53/
p 5-58
High freq.
P 5-51/
P 5-56
Low
ref.
value
P 5-52/
p 5-57
Illustration 3.24
5-50 Term. 29 Low Frequency
Range:
Function:
100 Hz
*
[0 - 110000
Hz]
Enter the low frequency limit
corresponding to the low motor shaft
speed (i.e. low reference value) in
5-52 Term. 29 Low Ref./Feedb. Value
Refer to the diagram in this section.
5-51 Term. 29 High Frequency
Range:
Function:
100 Hz
*
[0 - 110000
Hz]
Enter the high frequency limit
corresponding to the high motor shaft
speed (i.e. high reference value) in
5-53 Term. 29 High Ref./Feedb. Value
5-52 Term. 29 Low Ref./Feedb. Value
Range:
Function:
0
*
[-999999.999 -
999999.999 ]
Enter the low reference value limit for
the motor shaft speed [RPM]. This is
also the lowest feedback value, see
also
.
5-53 Term. 29 High Ref./Feedb. Value
Range:
Function:
100
*
[-999999.999 -
999999.999 ]
Enter the high reference value
[RPM] for the motor shaft speed
and the high feedback value, see
also
5-58 Term. 33 High Ref./Feedb.
Parameter Description
VLT
®
Refrigeration Drive Programming Guide
68
MG16H102 - VLT
®
is a registered Danfoss trademark
3
3