26-35 Term. X42/5 High Ref./Feedb. Value
Range:
Function:
100
*
[-999999.999 -
999999.999 ]
Enter the analog input scaling
value that corresponds to the high
voltage value set in
.
26-36 Term. X42/5 Filter Time Constant
Range:
Function:
0.001 s
*
[0.001 - 10
s]
Enter the time constant. This is a first-
order digital low pass filter time constant
for suppressing noise in terminal X42/5. A
high time constant value improves
dampening but also increases the time
delay through the filter.
NOTE
This parameter cannot be adjusted
while the motor is running.
26-37 Term. X42/5 Live Zero
Option:
Function:
This parameter makes it possible to enable the
Live Zero monitoring. E.g. where the analog input
is a of the frequency converter control, rather
than being used as of a decentral I/O system,
such as a Building Management System.
[0]
Disabled
[1]
*
Enabled
3.20.5 26-4* Analog Input X42/7
26-40 Terminal X42/7 Output
Option:
Function:
Set the function of terminal X42/7 as
an analog voltage output.
[0]
*
No operation
[100] Output frequency
0-100 Hz, (0-20 mA)
[101] Reference
Minimum reference - Maximum
reference, (0-20 mA)
[102] Feedback
-200% to +200% of
3-03 Maximum
Reference
, (0-20 mA)
[103] Motor Current
0 - Inverter Max. Current (
), (0-20 mA)
[104] Torque rel to limit
0 - Torque limit (
), (0-20 mA)
[105] Torq relate to
rated
0 - Motor rated torque, (0-20 mA)
[106] Power
0 - Motor rated power, (0-20 mA)
26-40 Terminal X42/7 Output
Option:
Function:
[107] Speed
0 - Speed High Limit (
and
), (0-20 mA)
[108] Torque
[109] Max Out Freq
[113] Ext. Closed Loop 1 0-100%, (0-20 mA)
[114] Ext. Closed Loop 2 0-100%, (0-20 mA)
[115] Ext. Closed Loop 3 0-100%, (0-20 mA)
[139] Bus ctrl.
0-100%, (0-20 mA)
[141] Bus ctrl t.o.
0-100%, (0-20 mA)
26-41 Terminal X42/7 Min. Scale
Range:
Function:
0 %
*
[0 -
200 %]
Scale the minimum output of the selected
analog signal at terminal X42/7, as a percentage
of the maximum signal level. E.g. if a 0 V (or 0
Hz) is desired at 25% of the maximum output
value. Then programme 25%. Scaling values up
to 100% can never be higher than the
corresponding setting in
.
See principle graph for
.
26-42 Terminal X42/7 Max. Scale
Range:
Function:
100
%
*
[0 -
200
%]
Scale the maximum output of the selected analog
signal at terminal X42/7. Set the value to the
maximum value of the voltage signal output. Scale
the output to give a voltage lower than 10 V at full
scale; or 10 V at an output below 100% of the
maximum signal value. If 10 V is the desired output
current at a value between 0-100% of the full-scale
output, programme the percentage value in the
parameter, i.e. 50% = 10 V. If a voltage between 0
and 10 V is desired at maximum output, calculate
the percentage as follows:
(
10
V
desired maximum voltage
)
x 100 %
i.e.
5
V : 10V
5
V × 100 % = 200 %
See principle graph for
6-52 Terminal 42 Output Max Scale
26-43 Terminal X42/7 Bus Control
Range:
Function:
0 %
*
[0 - 100 %] Holds the level of terminal X42/7 if
controlled by bus.
Parameter Description
VLT
®
Refrigeration Drive Programming Guide
MG16H102 - VLT
®
is a registered Danfoss trademark
161