6-50 Terminal 42 Output
Option:
Function:
[141]
Bus ctrl t.o.
0-100%, (0-20 mA)
[142]
Bus ctrl t.o. 4-20mA 0-100%
[143]
Ext. CL 1 4-20mA
0-100%
[144]
Ext. CL 2 4-20mA
0-100%
[145]
Ext. CL 3 4-20mA
0-100%
[150]
Max Out Fr 4-20 mA
NOTE
Values for setting the Minimum Reference is found in open
loop
and for closed loop
20-13 Minimum Reference/Feedb.
- values for maximum
reference for open loop is found in
3-03 Maximum
Reference
and for closed loop
20-14 Maximum Reference/
Feedb.
.
6-51 Terminal 42 Output Min Scale
Range:
Function:
0 %
*
[0 - 200
%]
Scale for the minimum output (0 or 4 mA) of
the analog signal at terminal 42.
Set the value to be the percentage of the full
range of the variable selected in
6-52 Terminal 42 Output Max Scale
Range:
Function:
100
%
*
[0 -
200
%]
Scale for the maximum output (20mA) of the
analog signal at terminal 42.
Set the value to be the percentage of the full
range of the variable selected in
.
130BA075.12
(mA)
0%
20
0/4
100%
Current
Analogue
output
Min Scale
par. 6-93
Variable
for
output
example:
Speed
(RPM)
Analogue
Output
Max Scale
par. 6-94
Illustration 3.27
It is possible to get a value lower than 20mA at
full scale by programming values >100% by using
a formula as follows:
20
mA / desired maximum current × 100 %
i.e. 10mA : 20 mA
10
mA × 100 % = 200 %
EXAMPLE 1:
Variable value= OUTPUT FREQUENCY, range = 0-100 Hz
Range needed for output = 0-50 Hz
Output signal 0 or 4mA is needed at 0 Hz (0% of range) -
set
6-51 Terminal 42 Output Min Scale
to 0%
Output signal 20 mA is needed at 50 Hz (50% of range) -
set
6-52 Terminal 42 Output Max Scale
to 50%
0/4 mA
20 mA
50%
100%
0%
50Hz
100Hz
0Hz
130BA858.10
Illustration 3.28
EXAMPLE 2:
Variable= FEEDBACK, range= -200% to +200%
Range needed for output= 0-100%
Output signal 0 or 4 mA is needed at 0% (50% of range) -
set
6-51 Terminal 42 Output Min Scale
to 50%
Output signal 20 mA is needed at 100% (75% of range) -
set
6-52 Terminal 42 Output Max Scale
to 75%
0/4 mA
20 mA
50%
75%
100%
0%
0%
+100%
+200%
-200%
130BA856.10
Illustration 3.29
EXAMPLE 3:
Variable value= REFERENCE, range= Min ref - Max ref
Range needed for output= Min ref (0%) - Max ref (100%),
0-10 mA
Output signal 0 or 4 mA is needed at Min ref - set
6-51 Terminal 42 Output Min Scale
to 0%
Output signal 10 mA is needed at Max ref (100% of range)
- set
6-52 Terminal 42 Output Max Scale
to 200%
(20 mA/10 mA x 100%=200%).
Parameter Description
VLT
®
Refrigeration Drive Programming Guide
76