6-40 Terminal X30/12 Low Voltage
Range:
Function:
0.07 V
*
[ 0 - par. 6-41
V]
Sets the analog input scaling value to
correspond to the low reference/
feedback value set in
6-41 Terminal X30/12 High Voltage
Range:
Function:
10 V
*
[ par. 6-40 - 10
V]
Sets the analog input scaling value to
correspond to the high reference/
feedback value set in
6-44 Term. X30/12 Low Ref./Feedb. Value
Range:
Function:
0
*
[-999999.999 -
999999.999 ]
Sets the analog output scaling value
to correspond to the low voltage
value set in
6-45 Term. X30/12 High Ref./Feedb. Value
Range:
Function:
100
*
[-999999.999 -
999999.999 ]
Sets the analog input scaling value
to correspond to the high voltage
value set in
.
6-46 Term. X30/12 Filter Time Constant
Range:
Function:
0.001 s
*
[0.001 - 10 s] A 1
st
order digital low pass filter time
constant for suppressing electrical noise
on terminal X30/12.
NOTE
This parameter cannot be changed while the motor is
running.
6-47 Term. X30/12 Live Zero
Option:
Function:
This parameter makes it possible to disable the
Live Zero monitoring. E.g. to be used if the
analog outputs are used as of a decentral I/O
system (e.g. when not of any frequency converter
related control functions, but feeding a Building
Management System with data)
[0]
*
Disabled
[1]
Enabled
3.8.7 6-5* Analog Output 1
Parameters for configuring the scaling and limits for
analog output 1, i.e. Terminal 42. Analog outputs are
current outputs: 0/4-20 mA. Common terminal (terminal
39) is the same terminal and has the same electrical
potential for analog common and digital common
connection. Resolution on analog output is 12 bit.
6-50 Terminal 42 Output
Option:
Function:
Select the function of Terminal 42
as an analog current output. A
motor current of 20 mA
corresponds to I
max
.
[0]
No operation
[100]
Output frequency
0-100 Hz, (0-20 mA)
[101]
Reference
Minimum reference - Maximum
reference, (0-20 mA)
[102]
Feedback
-200% to +200% of
20-14 Maximum
Reference/Feedb.
, (0-20 mA)
[103]
Motor Current
0 - Inverter Max. Current (
), (0-20 mA)
[104]
Torque rel to limit
0 - Torque limit (
), (0-20 mA)
[105]
Torq relate to rated 0 - Motor rated torque, (0-20 mA)
[106]
Power
0 - Motor rated power, (0-20 mA)
[107]
Speed
0 - Speed High Limit (
and
4-14 Motor Speed High Limit [Hz]
),
(0-20 mA)
[108]
Torque
[109]
Max Out Freq
[113]
Ext. Closed Loop 1
0-100%, (0-20 mA)
[114]
Ext. Closed Loop 2
0-100%, (0-20 mA)
[115]
Ext. Closed Loop 3
0-100%, (0-20 mA)
[130]
Output freq.
4-20mA
0-100 Hz
[131]
Reference 4-20mA
Minimum Reference - Maximum
Reference
[132]
Feedback 4-20mA
-200% to +200% of
20-14 Maximum
Reference/Feedb.
[133]
Motor cur. 4-20mA
0 - Inverter Max. Current (
[134]
Torq.% lim 4-20 mA 0 - Torque limit (
[135]
Torq.% nom
4-20mA
0 - Motor rated torque
[136]
Power 4-20mA
0 - Motor rated power
[137]
*
Speed 4-20mA
0 - Speed High Limit (4-13 and
4-14)
[138]
Torque 4-20mA
[139]
Bus ctrl.
0-100%, (0-20 mA)
[140]
Bus ctrl. 4-20 mA
0-100%
Parameter Description
VLT
®
Refrigeration Drive Programming Guide
MG16H102 - VLT
®
is a registered Danfoss trademark