4 All about FCD 300
4.1 Service
4.1.1 Diagnostics
The actual status can be read on the outside of the FCD products. Five LEDs signal the actual status of the unit with the meaning described in the table.
Further detailed status information can be obtained using a local control panel (LCP2 – see photo). This can be connected on the outside (without opening
the enclosure) if the LCP2-plug shown on the drawing is installed. The LCP2 is an easy-to -navigate user-friendly interface used to access and adjust all
parameters. It displays parameters in six different languages.
The FCD 300 holds a log with valuable information on failure. Information on the most recent 10 faults is stored and indexed in three different parameters
to help diagnosis.
Illustration 4.1: LCP2-plug
Parameter 616
stores the time of the fault as measured by the internal
clock.
Paramet er 617
holds a fault code telling the type of fault detected.
Parameter 618
stores a measurement relevant for the case. Typically
the intermediate circuit voltage or output current measured immediately
before failure.
Illustration 4.2: Local Control Panel
VLT® Decentral FCD
4 All about FCD 300
MG.04.B8.02 - VLT is a registered Danfoss trademark
87