512
Telegram Profile
Value:
Profidrive (Profidrive)
[0]
FC protocol (FC protocol)
[1]
Fast I/O FC-profile (Fast I/O FC-profile)
[2]
Function:
It is possible to choose between three different control word profiles.
Description of choice:
Select the desired control word profile.
See
Serial port for FCD 300
for further details of control word profiles.
513
Bus time interval
Value:
1 - 99 sec.
1 sec.
Function:
In this parameter it is possible to preset the maximum time expected to
elapse between receipt of two consecutive telegrams. If this time is ex-
ceeded, the serial communication is assumed to have stopped and the
desired reaction is preset in parameter 514
Bus time interval function
.
Description of choice:
Preset the required time.
514
Bus time interval function
Value:
Off (off)
[0]
Freeze output frequency (FREEZE OUTPUT)
[1]
Stop (STOP)
[2]
Jogging (JOGGING)
[3]
Max. speed (MAX SPEED)
[4]
Stop and trip (STOP AND TRIP)
[5]
Function:
In this parameter you can select the required reaction for the frequency
converter when the preset time in parameter 513
Bus time interval
has
been exceeded. If choices [1] to [5] are activated the output relay will be
deactivated.
Description of choice:
The output frequency of the frequency converter can be frozen at the
present value, stop the motor, be frozen at parameter 213
Jogging fre-
quency
, be frozen at parameter 202
Output frequency, high limit f
MAX
or stop and activate a cut out.
515-544 Data readout
Value:
Par.
no.
Description
Display text
Unit
515
Res. reference
(REFERENCE %)
%
516
Res. reference [Unit]
(REFERENCE [UNIT])
Hz, rpm
517
Feedback [Unit]
(FEEDBACK [UNIT])
Par. 416
518
Frequency
(FREQUENCY)
Hz
519
Frequency x scale
(FREQUENCY X SCALE)
Hz
520
Motor current
(MOTOR CURRENT)
Amp
521
Torque
(TORQUE)
%
522
Power[kW]
(POWER (KW))
kW
523
Power[HP]
(POWER (HP))
HP
524
Motor voltage
(MOTOR VOLTAGE)
V
525
DC-link voltage
(DC LINK VOLTAGE)
V
526
Thermal load motor
(MOTOR THERMAL)
%
527
Thermal load inverter
(INV. THERMAL)
%
528
Digital input
(DIGITAL INPUT)
Bin
529
Term.53, analogue input
(ANALOG INPUT 53)
V
531
Term.60, analogue input
(ANALOG INPUT 60)
mA
532
Term. 33, pulse input
(PULSE INPUT 33)
Hz
533
External ref.
(EXT. REF.%)
%
534
Status word, Hex
(STATUS WORD)
Hex
537
Inverter temperature
(INVERTER TEMP.)
°C
538
Alarm word
(ALARM WORD)
Hex
539
Control word
(CONTROL WORD)
Hex
540
Warning word
(WARN. WORD)
Hex
541
Extended status word
(EXT. STATUS WORD)
Hex
544
Pulse count
(PULSE COUNT)
545
Term. 29, pulse input
(PULSE INPUT 29)
Hz
Function:
These parameters can be read out via the serial communication port and
the LCP display. See also parameters 009-012
Display readout
.
NB!
Parameters 515-541 can only be read out via the serial
communication port.
Description of choice:
Resulting reference %, parameter 515:
Gives the resulting reference as a percentage in the range from Minimum
reference, Ref
MIN
to Maximum reference, Ref
MAX
. See also
Dealing with
references
.
Resulting reference [unit], parameter 516:
3 Programming
VLT® Decentral FCD
82
MG.04.B8.02 - VLT is a registered Danfoss trademark
3