Bit
Bit =0
Bit =1
00
Control ready
01
Drive ready
02
Coasting stop
03
No trip
Trip
04
Not used
05
Digital input 27
0: Input LOW/
1: Input HIGH
06
Trip lock
07
No warning
Warning
08
Speed
≠
ref.
Speed = ref.
09
Local control
Ser. communication
10
Outside frequency range
Frequency limit OK
11
Motor OK
12
Digital input 18
0: Input LOW/
1: Input HIGH
13
Digital input 19
0: Input LOW/
1: Input HIGH
14
Digital input 29
0: Input LOW/
1: Input HIGH
15
Digital input 33
0: Input LOW/
1: Input HIGH
3.7.9 Control Word According to Fieldbus Profile
To select
Profidrive
in the control word, parameter 512
Telegram Profile
must be set to
Profidrive
[0].
The control word is used to send commands from a master (e.g. a PC) to
a slave (frequency converter). MasterSlave.
Bit
Bit = 0
Bit =1
00
OFF 1
ON 1
01
OFF 2
ON 2
02
OFF 3
ON 3
03
Coasting stop
04
Quick stop
05
Freeze outp. freq.
06
Ramp stop
Start
07
Reset
08
Bus jog 1
09
Bus jog 2
10
Data not valid
Data valid
11
Slow down
12
Catch-up
13
Select Setup (lsb)
14
Select Setup (msb)
15
Reversing
Bit 00-01-02, OFF1-2-3/ON1-2-3:
Bit 00-01-02 = '0' causes ramp stop, which uses the ramp time in pa-
rameters 207/208 or 209/210.
If
Relay 123
is selected in parameter 323
Relay output
, the output relay
will be activated when the output frequency is 0 Hz.
Bit 00-01-02 = '1' means that the frequency converter can start the motor
if the other starting conditions are fulfilled.
Bit 03, Coasting stop:
See description under
Control word according to FC protocol.
Bit 04, Quick stop:
See description under
Control word according to FC protocol.
Bit 05, Freeze output frequency:
See description under
Control word according to FC protocol.
Bit 06, Ramp stop/start:
See description under
Control word according to FC protocol.
Bit 07, Reset:
See description under
Control word according to FC protocol.
Bit 08, Jog 1:
Bit 08 = "1" means that the output frequency is determined by parameter
09
Bus jog 1
.
Bit 09, Jog 2:
Bit 09 = "1" means that the output frequency is determined by parameter
510
Bus jog 2
.
Bit 10, Data not valid/Data valid:
See description under
Control word according to FC protocol.
Bit 11, Slow-down:
Used to reduce the speed reference by the value in parameter 219
Catch-
up/slow-down reference
.
Bit 11 = '0' does not cause any change to the reference.
Bit 11 = '1' means that the reference is reduced.
Bit 12, Catch-up:
Used to increase the speed reference by the value in parameter 219
Catch-up/slow-down reference
.
Bit 12 = '0' does not cause any change to the reference.
3 Programming
VLT® Decentral FCD
76
MG.04.B8.02 - VLT is a registered Danfoss trademark
3