Description of choice:
Set the required time.
318
Function after time out
Value:
No operation (NO OPERATION)
[0]
Freeze output frequency
(FREEZE OUTPUT FREQ.)
[1]
Stop (stop)
[2]
Jog (jog)
[3]
Max. speed (MAX SPEED)
[4]
Stop and trip (STOP AND TRIP)
[5]
Function:
This parameter allows a choice of the function to be activated after the
expiry of the Time out (parameter 317
Time out
). If a time-out function
occurs at the same time as a bus time-out function (parameter 513
Bus
time interval function
), the time-out function in parameter 318 will be
activated.
Description of choice:
The output frequency of the adjustable frequency drive can be:
-
frozen at the present frequency [1]
-
overruled to stop [2]
-
overruled to jog frequency [3]
-
overruled to max. output frequency [4]
-
overruled to stop with subsequent trip [5]
319
Analogue output terminal 42
Value:
No function (NO OPERATION)
[0]
External reference min.-max. 0-20 mA
(ref min-max = 0-20 mA)
[1]
External reference min.-max. 4-20 mA
(ref min-max = 4-20 mA)
[2]
Feedback min.-max. 0-20 mA
(fb min-max = 0-20 mA)
[3]
Feedback min.-max. 4-20 mA
(fb min-max = 4-20 mA)
[4]
Output frequency 0-max 0-20 mA
(0-fmax = 0-20 mA)
[5]
Output frequency 0-max 4-20 mA
(0-fmax = 4-20 mA)
[6]
Output current 0-I
INV
0-20 mA
(0-iinv = 0-20 mA)
[7]
Output current 0-I
IINV
4-20 mA
(0-iinv = 4-20 mA)
[8]
Output power 0-P
M,N
0-20 mA
(0-Pnom = 0-20 mA)
[9]
Output power 0-P
M,N
4-20 mA
(0-Pnom = 4-20 mA)
[10]
Inverter temperature 20-100 °C 0-20 mA
(TEMP 20-100 C=0-20 mA)
[11]
Inverter temperature 20-100 °C 4-20 mA
(TEMP 20-100 C=4-20 mA)
[12]
Function:
The analogue output can be used for stating a process value. It is possible
to choose two types of output signals 0 - 20 mA or 4 - 20 mA.
If used as a voltage output (0 - 10 V), a pull-down resistor of 500
Ω
must
be fitted to common (terminal 55). If the output is used as a current
output the resulting resistance from the equipment connected may not
exceed 500
Ω
.
Description of choice:
No function
. Is selected if the analogue output is not to be used.
External Ref
MIN
- Ref
MAX
0-20 mA/4-20 mA.
An output signal is obtained, which is proportional to the resulting refer-
ence value in the interval Minimum reference, Ref
MIN
- Maximum refer-
ence, Ref
MAX
(parameters 204/205).
FB
MIN
-FB
MAX
0-20 mA/ 4-20 mA.
An output signal is obtained, which is proportional to the feedback value
in the interval Minimum feedback, FB
MIN
- Maximum feedback, FB
MAX
(pa-
rameter 414/415).
0-f
MAX
0-20 mA/4-20 mA.
An output signal is obtained, which is proportional to the output frequen-
cy in the interval 0 - f
MAX
(parameter 202
Output frequency, high limit,
f
MAX
).
0 - I
INV
0-20 mA/4-20 mA.
An output signal is obtained, which is proportional to the output current
in the interval 0 - I
INV
0 - P
M,N
0-20 mA/4-20 mA.
An output signal is obtained, which is proportional to the present output
power. 20 mA corresponds to the value set in parameter 102
Motor
power, P
M,N
.
0 - Temp.
MAX
0-20 mA/4-20 mA.
An output signal is obtained, which is proportional to the present heatsink
temperature. 0/4 mA corresponds to a heatsink temperature of less than
20 °C, and 20 mA corresponds to 100 °C.
323
Relay output 1-3
Value:
No function (no operation)
[0]
Unit ready (unit ready)
[1]
Enable/no warning (enable/no warning)
[2]
Running (RUNNING)
[3]
Running in reference, no warning
(run on ref/no warn)
[4]
Running, no warnings
(RUNNING/NO WARNING)
[5]
Running in reference range, no warnings
(RUN IN RANGE/ NO WARN)
[6]
Ready - mains voltage within range
(RDY NO OVER/UNDERVOL)
[7]
Alarm or warning
(ALARM OR WARNING)
[8]
Current higher than current limit, par. 221
(Current limit)
[9]
Alarm (ALARM)
[10]
Output frequency higher than f
LOW
par. 225
(above frequency low)
[11]
3 Programming
VLT® Decentral FCD