PNU #
Parameterdescription
Factory setting
Changes during
operation
4-setup
Conv.
index
Data
type
302
Digital input, term. 18
Start
Yes
Yes
0
5
303
Digital input, term. 19
Reversing
Yes
Yes
0
5
304
Digital input, term. 27
Reset and coast inverse
Yes
Yes
0
5
305
Digital input, term. 29
Jog
Yes
Yes
0
5
307
Digital input, term. 33
No function
Yes
Yes
0
5
308
Term. 53, analogue input voltage
Reference
Yes
Yes
0
5
309
Term. 53, min scaling
0.0 V
Yes
Yes
-1
6
310
Term. 53, max scaling
10.0 V
Yes
Yes
-1
6
314
Term. 60, analogue input current
No function
Yes
Yes
0
5
315
Term. 60, min scaling
0.0 mA
Yes
Yes
-4
6
316
Term. 60, max scaling
20.0 mA
Yes
Yes
-4
6
317
Time out
10 sec.
Yes
Yes
-1
5
318
Function after timeout
No function
Yes
Yes
0
5
319
Term. 42, analogue output
0-I
MAX
= 0-20 mA
Yes
Yes
0
5
323
Relay output
No function
Yes
Yes
0
5
327
Pulse Max. 33
5000 Hz
Yes
Yes
0
7
328
Pulse Max. 29
5000 Hz
Yes
Yes
0
7
341
Term. 46 digital output
No function
Yes
Yes
0
5
342
Term. 46 Max. pulse output
5000 Hz
Yes
Yes
0
6
343
Precise stop function
Normal ramp stop
No
Yes
0
5
344
Counter value
100000 pulses
No
Yes
0
7
349
Speed comp delay
10 ms
Yes
Yes
-3
6
PNU #
Parameter description
Factory setting
Changes during
operation
4-setup
Conv.
index
Data
type
400
Brake function
Depends on unit type
Yes
No
0
5
405
Reset function
Manual reset
Yes
Yes
0
5
406
Aut. restart time
5 sec.
Yes
Yes
0
5
409
Trip delay overcurrent
Off (61 sec.)
Yes
Yes
0
5
411
Switching frequency
4.5 kHz
Yes
Yes
0
6
413
Overmodulation function
On
Yes
Yes
0
5
414
Min. feedback
0.000
Yes
Yes
-3
4
415
Max. feedback
1500.000
Yes
Yes
-3
4
416
Process units
No unit
Yes
Yes
0
5
417
Speed PID propor.ampl.
0.010
Yes
Yes
-3
6
418
Speed PID intergra.
100 ms
Yes
Yes
-5
7
419
Speed PID differentiation time
20.00 ms
Yes
Yes
-5
7
420
Speed PID diff. amplification limit
5.0
Yes
Yes
-1
6
421
Speed PID lowpass filter
20 ms
Yes
Yes
-3
6
423
U1 voltage
par. 103
Yes
Yes
-1
6
424
F1 frequency
Par. 104
Yes
Yes
-1
6
425
U2 voltage
par. 103
Yes
Yes
-1
6
426
F2 frequency
par. 104
Yes
Yes
-1
6
427
U3 voltage
par. 103
Yes
Yes
-1
6
428
F3 frequency
par. 104
Yes
Yes
-1
6
437
Proc. PID no/inv.
Normal
Yes
Yes
0
5
438
Proc. PID anti wind.
Active
Yes
Yes
0
5
439
Proc. PID start frequency
Par. 201
Yes
Yes
-1
6
440
Proc. PID start proportional ampl.
0.01
Yes
Yes
-2
6
441
Proc. PID integration time
Off (9999.99 s)
Yes
Yes
-2
7
442
Proc. PID differentiation time
Off (0.00 s).
Yes
Yes
-2
6
443
Proc. PID diff. ampl. limit
5.0
Yes
Yes
-1
6
444
Proc. PID lowpass filter time
0.02 s
Yes
Yes
-2
6
445
Flying start
Not possible
Yes
Yes
0
5
451
Speed PID feedforward factor
100%
Yes
Yes
0
6
452
Controller range
10 %
Yes
Yes
-1
6
455
Frequency range monitor
Enable
Yes
0
5
456
Brake voltage reduce
0
Yes
Yes
0
5
VLT® Decentral FCD
4 All about FCD 300
MG.04.B8.02 - VLT is a registered Danfoss trademark