NB!
In the
connection examples
below, it should be noted, that the Switch S100 must not be changed from factory settings (on).
2.6.1 Start/Stop
Start/stop using terminal 18 and coasting stop using terminal 27.
Par. 302
Digital input
=
Start
[7]
Par. 304
Digital input
=
Coasting stop inverted
[2]
For Precise start/stop the following settings are made:
Par. 302
Digital input
=
Precise start/stop
[27]
Par. 304
Digital input
=
Coasting stop inverted
[2]
2.6.2 Pulse Start/Stop
Pulse start using terminal 18 and pulse stop using terminal 19. In addition, the jog frequency is activated via terminal 29.
Par. 302
Digital input
=
Pulse start
[8]
Par. 303
Digital input
=
Stop inverted
[6]
Par. 304
Digital input
=
Coasting stop inverted
[2]
Par. 305
Digital input
=
Jog
[13]
2.6.3 Speed Up/Down
Speed up/down using terminals 29/33.
Par. 302
Digital input
=
Start
[7]
Par. 303
Digital input
=
Freeze reference
[14]
Par. 305
Digital input
=
Speed up
[16]
Par. 307
Digital input
=
Speed down
[17]