NB!
When the [OK] key is activated, the counter is reset to
zero.
619
RESET RUNNING HOURS COUNTER
Value:
No reset (DO NOT RESET)
[0]
Reset (RESET COUNTER)
[1]
Function:
Resetting of parameter 601
Hours run
to zero.
Description of choice:
If
Reset
[1] is selected and you press the [OK] key, the frequency con-
verter's parameter 601 is reset to zero
Hours run
. This parameter cannot
be selected via serial communication.
NB!
When the [OK] key is activated the parameter is reset
to zero.
620
Operation Mode
Value:
Normal operation (NORMAL OPERATION)
[0]
Control card test (CONTROL CARD TEST)
[2]
Initialise (INITIALIZE)
[3]
Function:
In addition to its normal function, this parameter can be used to test the
control card.
There is also the opportunity to perform an initialisation at the factory
setting for all parameters in all Setups, with the exception of parameters
500
Address
, 501
Baudrate
, 600-605
Operating data
and 615-617
Fault
log
.
Description of choice:
Normal function [0] is used for normal operation of the motor.
Control card test [2] is selected if you wish to check the control card's
analog/digital inputs, analog/digital outputs, relay outputs and 10 V and
24 V voltages.
The test is performed as follows:
18 - 19 - 27 - 29 - 33 - 46 are connected.
20 - 55 are connected.
42 - 60 are connected.
01 - 50 are connected.
02 - 53 are connected.
03 - 31B are connected.
Use the following procedure for the control card test:
1.
Select control card test.
2.
Disconnect the mains voltage and wait until the light in the dis-
play has disappeared.
3.
Mount according to drawing and description.
4.
Connect the mains voltage.
5.
The frequency converter automatically undertakes a test of the
control card.
If the LEDs are flashing a code (4 LEDs alternatively), the control card
test has failed (see the section
Internal faults
for further details. Change
the control card to start up the frequency converter.
If the frequency converter comes into Normal/Display mode, the test is
OK. Remove the test connector and the frequency converter is ready for
operation. Parameter 620
Operating mode
is automatically set to
Normal
operation
[0].
Initialisation
[3] is selected if you wish to use the unit's factory setting.
Procedure for initialisation:
1.
Select
Initialisation
[3].
2.
Disconnect the mains voltage and wait until the light in the dis-
play has disappeared.
3.
Connect the mains voltage.
4.
An initialisation is performed in all parameters in all Setups, with
the exception of parameters 500
Address
, 501
Baudrate
,
600-605
Operating data
and 615-617
Fault log
.
621-642 Unit Information
Val-
ue:
Par.
no
Description
Display text
621
Unit type
(DRIVE TYPE)
624
Software version
(SOFTWARE VERSION)
625
LCP identification no.
(LCP VERSION)
626
Database identification no.
(DATABASE VER.)
627
Power parts version
(POWER UNIT DB ID)
628
Application option type
(APP. OPTION)
630
Communication option type
(COM. OPTION)
632
BMC software identification
(BMC-SOFTWARE ID)
634
Unit identification for communi-
cation
(UNIT ID)
635
Software parts no.
(SW. PART NO.)
640
Software version
(SOFTWARE VERSION)
641
BMC-software identification
(BMC2 SW)
642
Power card identification
(POWER ID)
Function:
The unit's main data can be read out from parameters 621 to 635
Name-
plate
using the LCP control unit or serial communication. Parameters 640
- 642 can also be seen on the unit's integral display.
Description of choice:
Parameter 621 Nameplate: Unit type:
Gives unit size and mains voltage.
Example: FCD 311 380-480 V.
Parameter 624 Nameplate: Software version no.
The unit's present software version number appears here.
Example: V 1.00
Parameter 625 Nameplate: LCP ID number:
The ID number of the unit's LCP appears here.
Example: ID 1.42 2 kB
Parameter 626 Nameplate: Database ID number:
The ID number of the software's database appears here.
Example: ID 1.14.
VLT® Decentral FCD
3 Programming
MG.04.B8.02 - VLT is a registered Danfoss trademark
85
3