i.e. it is possible to turn off the control word if you do
not wish to use it in connection with updating or reading
parameters.
Bit 11, Relay 01:
Bit 11 = “0” Relay not activated.
Bit 11 = “1” Relay 01 activated, provided
Control word
bit
has been chosen in parameter 323.
Bit 12, Digital output, terminal 46:
Bit 12 = “0” Digital output has not been activated.
Bit 12 = “1” Digital output has been activated, provided
Control word bit
has been chosen in parameter 341.
Bit 13/14, Selection of Setup:
Bits 13 and 14 are used to choose from the four menu
Setups according to the following table:
Setup
Bit 14
Bit 13
1
0
0
2
0
1
3
1
0
4
1
1
The function is only possible when
Multi-Setups
is se-
lected in parameter 004
Active Setup
.
Note: I parameter 507
Selection of Setup
a selection is
made to define how Bit 13/14 gates with the corre-
sponding function on the digital inputs.
Bit 15 Reversing:
Bit 15 = '0' causes no reversing.
Bit 15 = '1' causes reversing.
Note: In the factory setting reversing is set to
digital
in
parameter 506
Reversing
. Bit 15 only causes reversing
when either
Ser. communication
,
Logic or
or
Logic
and
is selected.
Status Word according to FC Profile
The status word is used to inform the master (e.g. a
PC) of the slave's (frequency converter) mode.
Slave•Master.
Bit
Bit = 0
Bit =1
00
Control ready
01
Drive ready
02
Coasting stop
03
No trip
Trip
04
Not used
05
Not used
06
Trip lock
07
No warning
Warning
08
Speed • ref.
Speed = ref.
09
Local control
Ser. communi.
10
Outside
frequency range
Frequency limit
OK
11
Motor running
12
13
Voltage warn.
14
Current limit
15
Thermal
warn.
Bit 00, Control ready:
Bit 00 = '1'. The frequency converter is ready for op-
eration.
Bit 00 = '0'. The frequency converter is not ready for
operation.
Bit 01, Drive ready:
Bit 01 = '1'. The frequency converter is ready for op-
eration, but there is an active coasting command via
the digital inputs or via serial communication.
Bit 02, Coasting stop:
Bit 02 = '0'. The frequency converter has released the
motor.
Bit 02 = '1'. The frequency converter can start the mo-
tor when a start command is given.
Bit 03, No trip/trip:
Bit 03 = '0' means that the frequency converter is not
in fault mode.
Bit 03 = '1' means that the frequency converter is trip-
ped, and that it needs a reset signal for operation to be
reestablished.
Bit 04, Not used:
Bit 04 is not used in the status word.
Bit 05, Not used:
Bit 05 is not used in the status word.
MG.27.E2.02 - VLT is a registered Danfoss trademark
117
Pr
ogr
a
mmi
ng