Motor voltage [V]
(Motor voltage [V])
[11]
DC link voltage [V]
(DC link voltage [V])
[12]
Thermal load motor [%]
(Motor thermal [%])
[13]
Thermal load [%]
(FC. thermal[%])
[14]
Running hours [Hours]
(RUNNING HOURS])
[15]
Digital input [Bin]
(Digital input[bin])
[16]
Analog input 53 [V]
(analog input 53 [V])
[17]
Analog input 60 [mA]
(analog input 60 [mA])
[19]
Pulse reference [Hz]
(Pulse ref. [Hz])
[20]
External reference [%]
(external ref. [%])
[21]
Status word [Hex] (Status word [hex])
[22]
Heatsink temperature [°C]
(Heatsink temp [°C])
[25]
Alarm word [Hex] (Alarm word [hex])
[26]
Control word [Hex] (Control word [Hex])
[27]
Warning word [Hex]
(warning word [Hex])
[28]
Extended status word [Hex]
(Ext. status [hex])
[29]
Communication option card warning
(COMM OPT WARN [HEX])
[30]
Pulse count
(PULSE COUNTER)
[31]
Power [W]
(POWER [W])
[32]
Function:
In this parameter you can select the data value that
you wish to display in the LCP 2 control unit display
line 2 when the frequency converter is switched on.
The display will also be included in the scrollbar in dis-
play mode. In parameters 010-012
Display readout
you
can select a further three data values, which are dis-
played in display line 1.
Description of choice:
No readout
can only be selected in parameters
010-012
Small display readout
.
Resulting reference [%]
gives, as a percentage, the re-
sulting reference in the range from Minimum refer-
ence, Ref
MIN
to Maximum reference, Ref
MAX
.
Reference [unit]
gives the resulting reference with unit
Hz in
Open loop
. In
Closed loop
the reference unit is
selected in parameter 416
Process units
.
Feedback [unit]
gives the resulting signal value using
the unit/scaling selected in parameter 414
Minimum
feedback, FB
LOW
, 415
Maximum feedback, FB
HIGH
and
416
Process units
.
Frequency [Hz]
gives the output frequency of the fre-
quency converter.
Output frequency x scaling [-]
equals the present output
frequency f
M
multiplied by the factor set in parameter
008
Display scaling of output frequency
.
Motor current [A]
gives the phase current of the motor
measured as an effective value.
Torque [%]
denotes the motor's present load in relation
to the motor's rated torque.
Power [kW]
gives the present power that the motor is
absorbing in kW.
Power [HP]
gives the present power that the motor is
absorbing in HP.
Motor voltage[V]
gives the voltage supplied to the mo-
tor.
DC link voltage [V]
gives the intermediate circuit voltage
of the frequency converter.
Thermal load motor [%]
gives the calculated/estimated
load on the motor. 100 % is the cut-out limit.
Thermal load [%]
gives the calculated/estimated ther-
mal load on the frequency converter. 100 % is the cut-
out limit.
Running hours [Hours]
gives the number of hours that
the motor has tun since the last reset in parameter 619
Reset of running hours counter
.
Digital input [Binary code]
gives the signal status from
the 5 digital inputs (18, 19, 27, 29 and 33). Terminal
18 corresponds to the bit on the extreme left. `0' = no
signal, `1' = signal connected.
Analog input 53 [V]
gives the voltage value of terminal
53.
Analog input 60 [mA]
gives the present value of termi-
nal 60.
Pulse reference [Hz]
gives the reference in Hz connec-
ted to terminal 33.
= factory setting, () = display text, [] = value for use in communication via serial communication port
62