617
Fault log: Value
(F.LOG: VALUE)
Value:
[Index 1 - 10] Value: 0 - 9999
Function:
In this parameter it is possible to see at which value a
trip occurred. The unit of the value depends on which
alarm is active in parameter 615
Fault log: Fault
code
.
Description of choice:
Read out as one value.
618
Reset of kWh counter
(RESET kWh COUNT)
Value:
No reset (DO NOT RESET)
[0]
Reset (RESET COUNTER)
[1]
Function:
Resetting parameter 602
kWh counter
to zero.
Description of choice:
If
Reset
[1]is selected and you press the [OK] key, the
frequency converter's kWh counter is reset to zero.
This parameter cannot be selected via serial commu-
nication.
NB!
When the [OK] key is activated, the coun-
ter is reset to zero.
619
RESET RUNNING HOURS COUNTER
(RESET RUN. HOUR)
Value:
No reset (DO NOT RESET)
[0]
Reset (RESET COUNTER)
[1]
Function:
Resetting of parameter 601
Hours run
to zero.
Description of choice:
If
Reset
[1] is selected and you press the [OK] key, the
frequency converter's parameter 601 is reset to zero
Hours run
. This parameter cannot be selected via se-
rial communication.
NB!
When the [OK] key is activated the pa-
rameter is reset to zero.
620
Operation Mode
(OPERATION MODE)
Value:
Normal operation (NORMAL OPERATION)
[0]
Control card test (CONTROL CARD TEST)
[2]
Initialise (INITIALIZE)
[3]
Function:
NB!
Please note, that the control card will be
different on DeviceNet units. See the De-
viceNet manual MG.90.BX.YY for further
details.
In addition to its normal function, this parameter can
be used to test the control card.
There is also the opportunity to perform an initialisation
at the factory setting for all parameters in all Setups,
with the exception of parameters 500
Address
, 501
Baudrate
, 600-605
Operating data
and 615-617
Fault
log
.
Description of choice:
Normal function [0] is used for normal operation of the
motor.
Control card test [2] is selected if you wish to check the
control card's analog/digital inputs, analog/digital out-
puts, relay outputs and 10 V and 24 V voltages.
The test is performed as follows:
27 - 29 - 33 - 46 are connected.
50 - 53 are connected.
42 - 60 are connected.
12 - relay terminal 01 is connected.
18 - relay terminal 02 is connected.
19 - relay terminal 03 is connected.
= factory setting, () = display text, [] = value for use in communication via serial communication port