Technical data, mains supply 1 x 220 - 240 V/3 x 200-240V
According to . international
standards
Type 2803
2805
2807
2811
2815
2822
2822
PD2
2840
2840
PD2
Output current
I
INV.
[A]
2.2
3.2
4.2
6.0
6.8
9.6
9.6
16
16
(3 x 200-240V)
I
MAX
(60s) [A]
3.5
5.1
6.7
9.6
10.8
15.3
10.6
25.6
17.6
Output power (230
V)
S
INV.
[KVA]
0.9
1.3
1.7
2.4
2.7
3.8
3.8
6.4
6.4
Typical shaft output
P
M,N
[kW] 0.37
0.55
0.75
1.1
1.5
2.2
2.2
3.7
3.7
Typical shaft output
P
M,N
[HP]
0.5
0.75
1.0
1.5
2.0
3.0
3.0
5.0
5.0
Max. cable cross
section, motor
[mm
2
/AWG]
1)
4/10
4/10
4/10
4/10
4/10
4/10
4/10
4/10
16/6
Input current
I
L,N
[A]
5.9
8.3
10.6
14.5
15.2
-
22.0
-
31.0
(1 x 220-240 V)
I
L,MAX
(60s) [A]
9.4
13.3
16.7
23.2
24.3
-
24.3
-
34.5
Input current
I
L,N
[A]
2.9
4.0
5.1
7.0
7.6
8.8
8.8
14.7
14.7
(3 x 200-240 V)
I
L,MAX
(60s) [A]
4.6
6.4
8.2
11.2
12.2
14.1
9.7
23.5
16.2
Max. cable cross
section, power
[mm
2
/AWG]
1)
4/10
4/10
4/10
4/10
4/10
4/10
4/10
4/10
16/6
Max. pre-fuses
IEC/UL
2)
[A] 20/20 20/20 20/20 20/20 20/20 20/20 35/35 25/25 50/50
Efficiency
3)
[%]
95
95
95
95
95
95
95
95
95
Power loss at 100%
load
[W]
24
35
48
69
94
125
125
231
231
Weight
[kg] 2.0
2.0
2.0
2.0
2.0
3,7
6.0
6.0
18.50
Enclosure
4
type IP 20
IP 20
IP 20
IP 20
IP 20
IP 20
IP 20
IP 20
IP 20/
NEMA
1
1. American Wire Gauge. Max. cable cross section is
the largest cable cross section that can be attached to
the terminals. Always observe national and local reg-
ulations.
2. Type gG pre-fuses must be used for installation ac-
cording to IEC rules. If you want to maintain UL/cUL
you must use pre-fuses of the type Bussmann KTN-R
200 V, KTS-R 500 V or Ferraz Shawmut, type ATMR
(max. 30A). The fuses must be placed for protection in
a circuit that is capable of supplying a maximum of
100,000 amps RMS (symmetrical), 500 V maximum.
3. Measured using a 25 m screened/armoured motor
cable with a rated load and rated frequency.
4. IP20 is standard for VLT 2805-2875, whereas
NEMA 1 is an option.
MG.27.E2.02 - VLT is a registered Danfoss trademark