PNU # Parameter-description
Factory setting
4-setup
Conv.
index
Data-
type
100
Configuration
Speed reg., open loop
Yes
0
5
101
Torque characteristics
Constant torque
Yes
0
5
102
Motor power P
M,N
depends on unit
Yes
1
6
103
Motor voltage U
M,N
depends on unit
Yes
-2
6
104
Motor frequency f
M,N
50 Hz
Yes
-1
6
105
Motor current I
M,N
depends on motor selected
Yes
-2
7
106
Rated motor speed
depends on par. 102
Yes
0
6
107
Automatic motor adjustment
Optimisation off
Yes
0
5
108
Stator resistance R
S
depends on motor selected
Yes
-3
7
109
Stator reactance X
S
depends on motor selected
Yes
-2
7
117
Resonance damping
OFF
Yes
0
6
119
High start torque
0.0 sec
Yes
-1
5
120
Start delay
0.0 sec
Yes
-1
5
121
Start function
Coast in start del.
Yes
0
5
122
Function at stop
Coast
Yes
0
5
123
Min. freq. for activation of
par. 122
0.1 Hz
Yes
-1
5
126
DC braking time
10 sec.
Yes
-1
6
127
DC brake engaging frequency
OFF
Yes
-1
6
128
Thermal motor protection
No protection
Yes
0
5
130
Start frequency
0.0 Hz
Yes
-1
5
131
Voltage at start
0.0 V
Yes
-1
6
132
DC brake voltage
0%
Yes
0
5
133
Start voltage
depends on unit
Yes
-2
6
134
Load compensation
100 %
Yes
-1
6
135
U/f-ratio
depends on unit
Yes
-2
6
136
Slip compensation
100 %
Yes
-1
3
137
DC hold voltage
0%
Yes
0
5
138
Brake cut out value
3.0 Hz
Yes
-1
6
139
Brake cut in frequency
3.0 Hz
Yes
-1
6
140
Current, minimum value
0%
Yes
0
5
142
Leak reactance
depends on motor selected
Yes
-3
7
143
Internal ventilator control
Automatic
Yes
0
5
144
AC brake factor
1.30
Yes
-2
5
146
Reset voltage vector
Off
Yes
0
5
MG.27.E2.02 - VLT is a registered Danfoss trademark