203
Reference range
(REFERENCE RANGE)
Value:
Min. reference - Max reference (min - max)
[0]
-Max. reference - Max. reference
(-max - +max)
[1]
Function:
In this parameter you select whether the reference
signal must be positive or whether it can be both pos-
itive and negative. The minimum limit may be a nega-
tive value, unless in parameter 100
Configuration
a
selection has been made of
Speed regulation, closed
loop
. You should select
Min ref. - Max. ref.
[0], if
Proc-
ess regulation, closed loop
[3] has been selected in
parameter 100
Configuration
.
Description of choice:
Select the required range.
204
Minimum reference, Ref
MIN
(Min.reference)
Value:
Par. 100
Config.
=
Open loop
[0].-100,000.000 - par. 205 Ref
MAX
0.000 Hz
Par. 100
Config.
=
Closed
loop
[1]/[3].-Par. 414
Mini-
mum feedback
- par. 205
Ref
MAX
0.000 rpm/par 416
Function:
Minimum reference is an expression of the minimum
possible value of the total of all references. If in pa-
rameter 100
Configuration
,
Speed regulation, closed
loop
[1] or
Process regulation, closed loop
[3] is selec-
ted, the minimum reference is limited by parameter
414
Minimum feedback
. Minimum reference is ignored
if the local reference is active.
The reference unit can be defined from the following
table:
Par. 100
Configuration
Unit
Open loop [0]
Hz
Speed reg, closed loop [1]
rpm
Process reg, closed loop [3]
Par. 416
Description of choice:
The minimum reference is preset if the motor has to
run at a minimum speed, regardless of whether the
resulting reference is 0.
205
Maximum reference, Ref
MAX
(max.reference)
Value:
Par. 100
Config.
=
Open loop
[0].Par. 204
Ref
MIN
- 1000.000 Hz
50.000 Hz
Par. 100
Config.
=
Closed
loop
[1]/[3]. Par. 204
Ref
MIN
- Par. 415
Max.
feedback
50.000 rpm/par 416
Function:
The maximum reference gives the highest value that
can be assumed by the sum of all references. If
Closed
loop
[1]/[3] is selected in parameter 100
Configuration
the maximum reference cannot exceed the value in
parameter 415
Maximum feedback
.
Maximum reference is ignored if the local reference is
active.
The reference unit can be defined from the following
table:
Par. 100
Configuration
Unit
Open loop [0]
Hz
Speed reg, closed loop [1]
rpm
Process reg, closed loop [3]
Par. 416
Description of choice:
Maximum reference is set, if the speed of the motor is
to be max. the set value, regardless of the whether the
resulting reference is greater than the maximum ref-
erence.
206
Ramp type
(Ramp type)
Value:
Linear (Linear)
[0]
Sin shaped (SIN SHAPED)
[1]
Sin
2
shaped (S-SHAPED 2)
[2]
Function:
You can choose between a linear, an S-shaped and
an S
2
ramp process.
Description of choice:
Select the required ramp type depending on the re-
quired acceleration/deceleration process.