No.
Description
Warning
Alarm
Trip
locked
2
Live zero error (LIVE ZERO ERROR)
X
X
X
4
Mains phase loss (MAINS PHASE LOSS)
X
X
X
5
Voltage warning high (DC LINK VOLTAGE HIGH)
X
6
Voltage warning low (DC LINK VOLTAGE LOW)
X
7
Overvoltage (DC LINK OVERVOLT)
X
X
X
8
Undervoltage (DC LINK UNDERVOLT)
X
X
X
9
Inverter overload (INVERTER TIME)
X
X
10
Motor overloaded ( MOTOR, TIME)
X
X
11
Motor thermistor (MOTOR THERMISTOR)
X
X
12
Current limit (CURRENT LIMIT)
X
X
13
Overcurrent (OVERCURRENT)
X
X
X
14
Earth fault (EARTH FAULT)
X
X
15
Switch mode fault (SWITCH MODE FAULT)
X
X
16
Short-circuit (CURR. SHORT CIRCUIT)
X
X
17
Serial communication timeout (STD BUS TIMEOUT)
X
X
18
HPFB bus timeout (HPFB TIMEOUT)
X
X
33
Out of frequency range (OUT FREQ RNG/ROT LIM)
X
34
HPFB communication fault (PROFIBUS OPT. FAULT)
X
X
35
Inrush fault (INRUSH FAULT)
X
X
36
Overtemperature (OVERTEMPERATURE)
X
X
37-45
Internal fault (INTERNAL FAULT)
X
X
50
AMT not possible
X
51
AMT fault re. nameplate data (AMT TYPE.DATA FAULT)
X
54
AMT wrong motor (AMT WRONG MOTOR)
X
55
AMT timeout (AMT TIMEOUT)
X
56
AMT warning during AMT (AMT WARN. DURING AMT)
X
99
Locked (LOCKED)
X
LED indication
Warning
yellow
Alarm
red
Trip locked
yellow and red
WARNING/ALARM 2: Live zero fault
The voltage or current signal on terminal 53 or 60 is
below 50% of the preset value in parameter 309 or 315
Terminal, min. scaling
.
WARNING/ALARM 4: Mains phase fault
No phase on mains supply side. Check the supply
voltage to the frequency converter. This fault is only
active in 3-phase mains supply. The alarm can also
occur when the load is pulsing. In this instance the
pulses must be dampened, e.g. using an inertia disc.
WARNING 5: Voltage warning high
If the intermediate circuit voltage (UDC) is higher than
Voltage warning high
the frequency converter will give
a warning and the motor will continue to run un-
changed. If the UDC remains above the voltage warn-
ing limit, the inverter will trip after a set time. The time
depends on the device, and is set at 5 - 10 sec. Note:
The frequency converter will trip with an alarm 7 (over-
voltage). A voltage warning can occur when the con-
nected mains voltage is too high. Check whether the
supply voltage is suitable for the frequency converter,
see
Technical data
. A voltage warning can also occur
if the motor frequency is reduced too quickly due to
ramp down time being too short.
WARNING 6: Voltage warning low
If the intermediate circuit voltage (UDC) is lower
than
Voltage warning low
the frequency converter will
give a warning and the motor will continue to run un-
changed. A voltage warning can occur when the con-
nected mains voltage is too low. Check whether the
supply voltage is suitable for the frequency converter,
see
Technical data
. When the frequency converter is
switched off a brief warning 6 (and warning 8) appears.
WARNING/ALARM 7: Overvoltage
If the intermediate voltage (UDC) goes over the inver-
ter's
Overvoltage limit
the inverter will be switched off
until the UDC has once more fallen below the over-
voltage limit. If the UDC remains above the overvoltag
limit the inverter will trip after a set time. The time de-
pends on the device, and is set at 5 - 10 sec. An
144
MG.27.E2.02 - VLT is a registered Danfoss trademark