Order form
This section makes it easier for you to specify and
order a VLT 2800.
Choice of frequency converter
The frequency converter must be chosen on the basis
of the present motor current at maximum loading of
the unit. The frequency converter's rated output cur-
rent I
INV.
must be equal to or greater than the required
motor current.
Mains voltage
VLT 2800 is available for two mains voltage ranges:
200-240 V and 380-480 V.
Select whether the frequency converter is connected
to a mains voltage of:
-
1 x 220 - 240 V single-phase AC voltage
-
3 x 200 - 240 V three-phase AC voltage
-
3 x 380 - 480 V three-phase AC voltage
1 x 220 - 240 Volt mains voltage
Typical shaft output
P
INV.
Max. constant output current I
INV.
Max. constant output power at
230 V S
INV.
Type
[kW]
[HP]
[A]
[kVA]
2803
0.37
0.5
2.2
0.9
2805
0.55
0.75
3.2
1.3
2807
0.75
1.0
4.2
1.7
2811
1.1
1.5
6.0
2.4
2815
1.5
2.0
6.8
2.7
2822
2.2
3.0
9.6
3.8
2840
3.7
5.0
16
6.4
3 x 200 - 240 Volt mains voltage
Typical shaft output
P
INV.
Max. constant output current I
INV.
Max. constant output power at
230 V S
INV.
Type
[kW]
[HP]
[A]
[kVA]
2803
0.37
0.5
2.2
0.9
2805
0.55
0.75
3.2
1.3
2807
0.75
1.0
4.2
1.7
2811
1.1
1.5
6.0
2.4
2815
1.5
2.0
6.8
2.7
2822
2.2
3.0
9.6
3.8
2840
3.7
5.0
16.0
6.4
MG.27.E2.02 - VLT is a registered Danfoss trademark
9
In
tro
duc
ti
on
to
VLT 280
0