Serial communication
500
Address
(BUS ADDRESS)
Value:
Parameter 500 Protocol = FC protocol [0]
0 - 247
1
Parameter 500 Protocol = Metasys N2 [1]
1 - 255
1
Parameter 500 Protocol = MODBUS RTU [3]
1 - 247
1
Function:
This parameter allows the allocation of an address to
each frequency converter in a serial communication
network.
Description of choice:
The individual frequency converter must be allocated
a unique address.
If the number of units connected (frequency converters
+ master) is higher than 31, a repeater must be used.
Parameter 500
Address
cannot be selected via the
serial communication, but must be preset via the con-
trol unit.
501
Baudrate
(BAUDRATE)
Value:
300 Baud (300 BAUD)
[0]
600 Baud (600 BAUD)
[1]
1200 Baud (1200 BAUD)
[2]
2400 Baud (2400 BAUD)
[3]
4800 Baud (4800 BAUD)
[4]
9600 Baud (9600 BAUD)
[5]
Function:
This parameter is for programming the speed at which
data is transmitted via the serial port. Baud rate is de-
fined as the number of bits transmitted per second.
Description of choice:
The frequency converter's transmission speed must
be set at a value corresponding to the transmission
speed of the master.
Parameter 501
Baudrate
cannot be selected via the
serial port, but must be preset via the operating unit.
502
Coasting Stop
(COASTING SELECT)
Value:
Digital input (DIGITAL INPUT)
[0]
Serial port (SERIAL PORT)
[1]
Logic and (LOGIC AND)
[2]
Logic or (LOGIC OR)
[3]
Function:
Parameters 502-508 allow a choice between control-
ling the frequency converter via the digital inputs and/
or via the serial port.
If
Serial port
[1] is selected, the relevant command can
only be activated if a command is given via the serial
port.
In the case of
Logic and
[2] the function must also be
activated via a digital input.
Description of choice:
The table below shows when the motor is running and
when it is coasting, when each of the following is se-
lected:
Digital input
[0],
Serial port
[1],
Logic and
[2] or
Logic or
[3].
NB!
Note that
Coasting stop
and Bit 03 in the
control word are active at logic '0'.
Digital input
[0]
Dig. input
Ser. port
Function
0
0
Coasting
0
1
Coasting
1
0
Motor running
1
1
Motor running
Serial port
[1]
Dig. input
Ser. port
Function
0
0
Coasting
0
1
Motor running
1
0
Coasting
1
1
Motor running
Logic and
[2]
Dig. input
Ser. port
Function
0
0
Coasting
0
1
Motor running
1
0
Motor running
1
1
Motor running
Logic or
[3]
Dig. input
Ser. port
Function
0
0
Coasting
0
1
Coasting
1
0
Coasting
1
1
Motor running
= factory setting, () = display text, [] = value for use in communication via serial communication port