display under “Setup”. It is also possible to preset the
frequency converter to
Multisetup
, so that it is possible
to shift Setups using the digital inputs or serial com-
munication. Setup shift can be used in a plant in which,
for example, one Setup is used for daytime operation
and another one at night time.In parameter 006
Setup
copying
it is possible to copy from one Setup to an-
other. Using parameter 007
LCP copy
all Setups can
be transferred from one frequency converter to anoth-
er by moving the LCP 2 control panel. First all param-
eter values are copied to the LCP 2 control panel,
which can then be moved to another frequency con-
verter. Here all parameter values can be copied from
the LCP 2 control unit to the frequency converter.
Setup shift
-
Selection of Setup via terminals 29 and 33.
Par. 305
Digital input
=
Selection of Setup,
lsb
[31]
Par. 307
Digital input
=
Selection of Setup,
msb
[32]
Par. 004
Active setup
=
Multi Setup
[5]
004
Active Setup
(active Setup)
Value:
Factory Setup (FACTORY SETUP)
[0]
Setup 1 (setup 1)
[1]
Setup 2 (setup 2)
[2]
Setup 3 (setup 3)
[3]
Setup 4 (setup 4)
[4]
Multi Setup (MULTI SETUP)
[5]
Function:
The active parameter Setup is selected here. All pa-
rameters can be programmed in four individual pa-
rameter Setups. Shifts between Setups can be made
in this parameter via a digital input or via serial com-
munication.
Description of choice:
Factory Setup
[0] contains the factory-set parameter
values.
Setup 1-4
[1]-[4] are four individual Setups
which can be selected as required.
Multi Setup
[5] is
used where remote-controlled shifts between the four
Setups via a digital input or via serial communication
is required.
005
Programming Setup
(EDIT SETUP)
Value:
Factory Setup (FACTORY SETUP)
[0]
Setup 1 (setup 1)
[1]
Setup 2 (setup 2)
[2]
Setup 3 (setup 3)
[3]
Setup 4 (setup 4)
[4]
Active Setup (ACTIVE SETUP)
[5]
Function:
You can select which Setup you want to programme
during operation (applies both via the control panel
and the serial communication port). It is, for example,
possible to programme
Setup 2
[2], while the active
Setup is set to
Setup 1
[1] in parameter 004
Active
Setup
.
Description of choice:
Factory Setup
[0] contains the factory-set data and can
be used as a source of data if the other Setups are to
be reset to a known status.
Setup 1-4
[1]-[4] are indi-
vidual Setups that can be programmed freely during
operation. If
Active Setup
[5] is selected, the program-
ming Setup will be equal to parameter 004
Active
Setup
.
NB!
If data is modified or copied to the active
Setup, the modifications have an immedi-
ate effect on the unit's operation.
= factory setting, () = display text, [] = value for use in communication via serial communication port
60