RFI 1B/LC filter
NB!
To comply with EN 55011-1B the RFI 1B
filter module must be fitted to a VLT 2800
with integral 1A RFI filter.
NB!
The 1B/LC filter is not suitable for 200 V
devices due to the high 1Ø input current.
Technical data for VLT 2803–2875 RFI 1B/LC filter
Max. cable length (screened/armoured) 380-480 V
25 m (At 1A: 50 m)
Enclosure
IP 20
Max. rated current
4.0 (Order no.: 195N3100); 9.1 (Order no.: 195N3101)
Max. voltage
480 V AC
Max. voltage to earth
300 V AC
Min. distance between VLT and RFI 1B/LC filter
Side-by-Side
Min. distance above and below RFI 1B/LC filter
100 mm
Dimensions 195N3100 4.0 A H x W x D (mm)
200 x 75 x 168
Dimensions 195N3101 9.1 A H x W x D (mm)
267.5 x 90 x 168
Weight 195N3100 4.0 A
2.4 kg
Weight 195N3101 9.1 A
4.0 kg
MG.27.E2.02 - VLT is a registered Danfoss trademark
15