020
Hand operation
(HAND OPERATION)
Value:
Not active (DISABLE)
[0]
Active (ENABLE)
[1]
Function:
In this parameter you can select whether it should be
possible or not to switch between Auto- and Hand
mode. In Auto mode the frequency converter is con-
trolled by external signals whereas the frequency con-
verter in Hand mode is controlled via a local reference
directly from the control unit.
Description of choice:
If
Not active
[0] is selected in this parameter, the Hand
mode function will be inactive. If
Active
[1] is selected
you can switch between Auto- and Hand mode. For
further information, see the
Control Unit
section.
024
Userdefined Quick Menu
(user quickmenu)
Value:
Not active (Disable)
[0]
Active (Enable)
[1]
Function:
In this parameter you can select the standard setup of
the Quick menu key on the control panel and the LCP
2 control panel.
Using this function, in parameter 025
Quick Menu set-
up
the user can select up to 20 parameters for the
Quick Menu key.
Description of choice:
If
not active
[0] is selected, the standard setup of the
Quick Menu key is active.
If
Active
[1] is selected, the user-defined Quick Menu
is active.
025
Quick Menu setup
(quick menu setup)
Value:
[Index 1 - 20] Value: 0 - 999
000
Function:
In this parameter you define which parameters are re-
quired in the Quick Menu when parameter 024
User-
defined Quick Menu
is set to
Active
[1].
Up to 20 parameters can be selected for the user-de-
fined Quick Menu.
NB!
Please note that this parameter can only
be set using an LCP 2 control panel.
See
Order form
.
Description of choice:
The Quick Menu is set up as follows:
1.
Select parameter 025
Quick Menu setup
and
press [CHANGE DATA].
2.
Index 1 indicates the first parameter in Quick
Menu. You can scroll between the index
numbers using the [+ / -] keys. Select Index
1.
3.
Using [< >] you can scroll between the three
figures. Press the [<] key once ad the last
number in the parameter number can be se-
lected using the [+ / -] keys. Set Index 1 to
100 for parameter 100
Configuration
.
4.
Press [OK] when Index 1 has been set to 100.
5.
Repeat steps 2 - 4 until all parameters re-
quired have been set to the Quick Menu key.
6.
Press [OK] to complete the Quick Menu set-
up.
If parameter 100
Configuration
is selected at Index 1,
Quick Menu will start with this parameter every time
Quick Menu is activated.
Please note that parameter 024
User-defined Quick
Menu
and parameter 025
Quick Menu setup
are reset
to the factory setting during initialisation.
= factory setting, () = display text, [] = value for use in communication via serial communication port
66