Control for 6/8 HP Outdoor Unit
SiAF332111E
72
Part 4 Functions and Control
2.5.3 Compressor Capacity Control
Te: Low pressure equivalent saturation temperature
Capacity steps
The compressor rotation speed is changed according to the control pressure.
Cooling: suction pressure sensor value is converted into evaporation saturated temperature
(relation between pressure and evaporating temperature based on characteristics of
refrigerant R-410A). For detailed explanation refer to chapter field settings
(Details of
Setting Mode (Mode 2)
on page 135 and installation manual outdoor chapter Energy saving
and optimum operation).
Initial selection is made between Automatic, Fixed or High sensible.
During operation, the outdoor target evaporating temperature can be changed based on
the selected sub function, taking indoor load into account.
The initial target saturated temperature can be changed. For details refer to
Details of
Setting Mode (Mode 2)
on page 135 for Cooling: Te set based on field setting 2-8.
During operation, outdoor control will take into account the pressure drop so that at indoor
units, the preset target temperature is reached (average). The estimated pressure drop is
calculated based on:
Pressure drop characteristics found during test-operation outdoor (step 7). At several
evaporating temperatures, outdoor control stores difference between outdoor
evaporating temperature and average of indoor heat exchanger (indoor evaporating
temperature).
To have judgment of gas speed in main suction pipe, control takes the capacity step of
the outdoor unit into account. In function of pressure drop characteristics at the different
compressor capacity steps, control concludes the category of system pipe lay out (long,
medium, short).
Target Te outdoor (cooling) = Te set – estimated pressure drop –
A
.
Correction factor
A
depends on the absolute value of the difference between indoor air inlet
temperature and a set temperature after startup period.
Содержание VRV S RXMQ10ARY1
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Страница 349: ...SiAF332111E Check Part 6 Service Diagnosis 343 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 366: ...SiAF332111E 360 Part 7 Appendix 1 Wiring Diagrams 361 1 1 Outdoor Unit 361 1 2 VRV Indoor Unit 366 Part 7 Appendix...
Страница 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Страница 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Страница 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Страница 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 376: ...Wiring Diagrams SiAF332111E 370 Part 7 Appendix 1 2 4 Wall Mounted FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...