SiAF332111E
Symptom-based Troubleshooting
Part 6 Service Diagnosis
179
2. Symptom-based Troubleshooting
Symptom
Supposed Cause
Countermeasure
1
The system does not start operation at all.
Blowout of fuse(s)
Turn Off the power supply and then
replace the fuse(s).
Cutout of breaker(s)
• If the knob of any breaker is in its
OFF position, turn ON the power
supply.
• If the knob of any circuit breaker is
in its tripped position, do not turn
ON the power supply.
Power failure
After the power failure is reset,
restart the system.
The connector loose or not fully
plugged in
Turn off the power supply to verify
the connection of the connector.
2
The system starts operation but makes an
immediate stop.
Blocked air inlet or outlet of indoor
or outdoor unit
Remove obstacle(s).
Clogged air filter(s)
Clean the air filter(s).
3
The system does not cool air well.
Blocked air inlet or outlet of indoor
or outdoor unit
Remove obstacle(s).
Clogged air filter(s)
Clean the air filter(s).
Enclosed outdoor unit(s)
Remove the enclosure.
Improper set temperature
Set the temperature to a proper
degree.
Airflow rate set to LOW
Set it to a proper airflow rate.
Improper direction of air diffusion
Set it to a proper direction.
Open window(s) or door(s)
Shut it tightly.
Cooling operation
Direct sunlight received
Hang curtains or shades on
windows.
Cooling operation
Too many people staying in a room
The model must be selected to
match the air conditioning load.
Cooling operation
Too many heat sources (e.g. OA
equipment) located in a room
Dry operation
The reason is that the dry operation
serves not to reduce the room
temperature where possible.
Change the system to cooling
operation.
4
The system does
not operate.
The system stops and
immediately restarts
operation.
If the operation lamp on the remote
controller turns ON, the system will
be normal. These symptoms
indicate that the system is
controlled so as not to put
unreasonable loads on the system.
Normal operation. The system will
automatically start operation after a
lapse of five minutes.
Pressing the temperature
setting button immediately
resets the system.
The system stops immediately
after turning ON the power
supply.
The system is in preparation mode
of microcomputer operation.
Wait for a period of approximately
one minute.
5
The system
makes
intermittent
stops.
The remote controller displays
error codes
U4
or
U5,
and the
system stops but restarts after
a lapse of several minutes.
The system stops due to an
interruption in communication
between units caused by electrical
noises coming from equipment
other than air conditioners.
Remove causes of electrical noises.
If these causes are removed, the
system will automatically restart
operation.
6
The system
conducts fan
operation but not
cooling
operation.
This symptom occurs
immediately after turning ON
the power supply.
The system is in preparation mode
of operation.
Wait for a period of approximately
10 minutes.
The remote controller displays
the mark for centralized
control; no cooling operation is
performed. Switch to fan
operation.
In thermal storage operation, the
unit is set to fan operation in cooling
operation, and the remote controller
shows the mark for centralized
control.
Normal operation.
O
N
Kno
b
Tripped
OFF
Circ
u
it
b
reaker
Содержание VRV S RXMQ10ARY1
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Страница 349: ...SiAF332111E Check Part 6 Service Diagnosis 343 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 366: ...SiAF332111E 360 Part 7 Appendix 1 Wiring Diagrams 361 1 1 Outdoor Unit 361 1 2 VRV Indoor Unit 366 Part 7 Appendix...
Страница 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Страница 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Страница 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Страница 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 376: ...Wiring Diagrams SiAF332111E 370 Part 7 Appendix 1 2 4 Wall Mounted FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...