SiAF332111E
Field Settings for Outdoor Unit (6/8 HP Models)
Part 5 Field Settings and Test Operation
139
Mode 2-29:
Capacity priority
. When the night-time low noise operation is in use,
performance of system might drop because airflow rate of outdoor unit is reduced.
Default value: 0. Capacity priority cannot be used.
Field setting 1: capacity priority can temporary cancel the night-time low noise operation.
Capacity priority can be initiated when certain operation parameters approach the safety
setting:
Raise in high pressure during cooling.
Raise of discharge pipe temperature.
Raise of inverter current.
Raise of fin temperature inverter PCB.
When operation parameters return to normal range, the capacity priority is switched OFF,
enable to reduce airflow rate depending on night-time low noise operation is still required
(end time for low night noise operation is not reached or external input night-time low
noise operation is still closed).
RXMQ8AR
Check 1
: AC power input 380-415 V unbalance max. 2%.
Check 2
: AC U/V/W 10 Hz intermediate: check difference within 10 V (at fasten U/V/W)
*Note: Actual voltage value depends on meter characteristics
±6 sec
±3 sec
Check 1
±100V
AC*
Step 2:
Mode
2-28
Set 02
Ѝ
01, then
press “Return” twice
OR press “MODE” button
Voltage
output
U/V/W
Check 2
Frequency: 10 Hz
Step 1:
Mode 2-28
Set 01
Ѝ
02, then
press
“Return” twice
Disconnect U/V/W from compressor before
performing the power transistor check.
Operation
sound
Rated
Level 1
Level 2
Level 3
Time set with night-time low
noise operation start setting
Low noise mode
instructing Operation sound
set with external low noise
setting
10:00 PM
8:00 PM
12:00 AM
6:00 AM 7:00 AM 8:00 AM
Set with night-time low noise operation start
setting. (Factory setting is 10:00 PM.)
Set with night-time low noise operation end
setting. (Factory setting is 8:00 AM.)
∗
Low noise
mode instructing
∗
Operation sound set with
external low noise setting
∗
Night-time
If capacity priority is set in
capacity priority setting, the fan
speed will be increased
according to the load of air
conditioning when load is heavier.
Time set with night-time low
noise operation end setting
∗
Operation sound mode
set with night-time low
noise operation setting
Содержание VRV S RXMQ10ARY1
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Страница 349: ...SiAF332111E Check Part 6 Service Diagnosis 343 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 366: ...SiAF332111E 360 Part 7 Appendix 1 Wiring Diagrams 361 1 1 Outdoor Unit 361 1 2 VRV Indoor Unit 366 Part 7 Appendix...
Страница 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Страница 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Страница 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Страница 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 376: ...Wiring Diagrams SiAF332111E 370 Part 7 Appendix 1 2 4 Wall Mounted FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...