SiAF332111E
Troubleshooting by Error Code
Part 6 Service Diagnosis
335
YES
NO
NO
NO
NO
YES
Does the data
station connect?
YES
Does the
parallel interface
connect?
NO
YES
YES
NO
YES
When troubleshooting fails
A
Not available for combined use of
schedule timer and parallel interface.
Dismount either, and then
concurrently reset the power supply
of all the centralized controllers.
Dismount the
Independent/Combined use
connector of the schedule
timer, and then concurrently
reset the power supply of all
the centralized controllers.
Integrate one unit for the
centralized controller
connected with the setting
connector, and then
concurrently reset the
power supply of all the
centralized controllers.
Disconnect the setting
connector of the main
centralized controller and
connect it to a different
centralized controller, and then
reset the power supply of all the
centralized controllers. If after
this the error is resolved, the
centralized controller connected
with the setting connector is
faulty. Replace the controller.
Not available for combined use of
schedule timer and data station.
Dismount either, and then
concurrently reset the power supply of
all the centralized controllers.
Not available for combined use with
the remote control adaptor. Dismount
the remote control adaptor, and then
concurrently reset the power supply of
all the centralized controllers.
YES
YES
NO
NO
Modify the setting of the
ON/OFF controller control
range setting switch.
Reset the power supply of
the ON/OFF controller.
Is the
ON/OFF
controller control range
setting switch set
duplicately?
Do two or
more ON/OFF controllers
connect?
Does
the schedule timer
connect?
Does the
Independent/Combined
use connector of the
schedule timer
connect?
Does the
remote control adaptor
connect?
Are
there two or
more centralized controllers
connected with setting
connectors?
Concurrently reset the power supply
of all the centralized controllers.
Содержание VRV S RXMQ10ARY1
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Страница 349: ...SiAF332111E Check Part 6 Service Diagnosis 343 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 366: ...SiAF332111E 360 Part 7 Appendix 1 Wiring Diagrams 361 1 1 Outdoor Unit 361 1 2 VRV Indoor Unit 366 Part 7 Appendix...
Страница 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Страница 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Страница 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Страница 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 376: ...Wiring Diagrams SiAF332111E 370 Part 7 Appendix 1 2 4 Wall Mounted FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...