Field Settings for Outdoor Unit (4/5 HP Models)
Part 5 Field Settings and Test Operation
117
2.3 Night-Time Low Noise Operation and Demand Operation
2.3.1 Night-Time Low Noise Operation
By connecting the external contact input to the low noise input of the outdoor unit external
control adaptor (optional), you can lower operating noise by 2-3 dB.
When night-time low noise operation is carried out automatically (External control
adaptor for outdoor unit is not required)
1. While in setting mode 2, select a night-time low noise operation level (i.e., Level 1, Level 2,
Level 3) for the item 2-22.
2. If necessary, while in setting mode 2, select a starting time of night-time low noise operation
(i.e., 8:00 PM, 10:00 PM, or 12:00 AM) for the item 2-26. (Use the starting time as a guide since
it is estimated according to outdoor temperatures.)
3. If necessary, while in setting mode 2, select an ending time of night-time low noise operation
(i.e., 6:00 AM, 7:00 AM, or 8:00 AM) for the item 2-27. (Use the ending time as a guide since it
is estimated according to outdoor air temperatures.)
4. If necessary, while in setting mode 2, set the item 2-29 (Capacity priority setting) to ON. (If the
condition is set to ON, when the air conditioning load reaches a high level, the system will be put
into normal operation mode even during night-time.)
Operation
so
u
nd
Rated
Le
v
el 1
Le
v
el 2
Le
v
el 3
Time set
w
ith night-time lo
w
noise
operation start setting
If capacity priority is set in
Capacity priority setting, the fan
speed
w
ill
b
e increased
according to the load of air
conditioning
w
hen load is hea
v
ier.
Time set
w
ith night-time lo
w
noise operation end setting
Operation so
u
nd d
u
ring
night-time lo
w
noise
operation mode can
b
e set
w
ith night-time lo
w
noise
operation le
v
el setting.
(Factory setting is OFF.)
N
ight-time
Operation so
u
nd le
v
el set
w
ith
night-time lo
w
noise operation
setting
6:00 AM
8
:00 PM 10:00 PM 12:00 AM
7:00 AM
8
:00 AM
Set
w
ith night-time lo
w
noise operation end setting.
(Factory setting is
8
:00 AM.)
Set
w
ith night-time lo
w
noise operation start setting.
(Factory setting is 10:00 PM.)
Содержание VRV S RXMQ10ARY1
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Страница 349: ...SiAF332111E Check Part 6 Service Diagnosis 343 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 366: ...SiAF332111E 360 Part 7 Appendix 1 Wiring Diagrams 361 1 1 Outdoor Unit 361 1 2 VRV Indoor Unit 366 Part 7 Appendix...
Страница 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Страница 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Страница 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Страница 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 376: ...Wiring Diagrams SiAF332111E 370 Part 7 Appendix 1 2 4 Wall Mounted FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...