Field Settings for Outdoor Unit (10/12 HP Models)
SiAF332111E
154
Part 5 Field Settings and Test Operation
Mode 2
Mode 2 is used to set field settings of the outdoor unit and system.
Changing and access the setting in mode 2:
To quit and return to the initial status, press BS1.
Changing the value of the selected setting in mode 2:
Once mode 2 is selected (press BS1 for more than 5 seconds) you can select the wanted
setting. It is done by pressing BS2.
Accessing the selected setting's value is done by pressing BS3 once.
Now BS2 is used to select the required value of the selected setting.
When the required value is selected, you can define the change of value by pressing BS3
once.
Press BS3 again to start operation according to the chosen value.
Example:
Checking the content of parameter [2-18] (to define the high static pressure setting of the
outdoor unit's fan).
[A-B]: C in this case defined as: A = 2; B = 18; C = the value we want to know/change
Make sure the segment indication is as during normal operation (default situation when
shipped from factory).
Press BS1 for over 5 seconds; result segment display:
Result: mode 2 is accessed.
Press BS2 18 times; result segment display:
Result: mode 2 setting 18 is addressed.
Press BS3 once; the value which is returned (depending on the actual field situation), is the
status of the setting. In the case of [2-18], default value is "0", which means the function is
not active.
Result: mode 2 setting 18 is addressed and selected, return value is the current setting
situation.
To change the value of the setting, press BS2 until the required value appears on the
segment indication. When achieved, define the setting value by pressing BS3 once. To start
operation according to the chosen setting, confirm again by pressing BS3.
To leave the field setting mode, press BS1 2 times, you will return to the default situation
when shipped from factory.
Operating the DIP switches
By operating the DIP switches it is possible to:
Once mode 2 is selected (press BS1 for more than 5 seconds), you can select the
wanted setting. It is done by pressing BS2.
Accessing the selected setting's value is done by pressing BS3 once.
What to do with DIP switch DS1
2-4
NOT USED
DO NOT CHANGE THE FACTORY SETTING
What to do with DIP switch DS2
1-4
NOT USED
DO NOT CHANGE THE FACTORY SETTING
Содержание VRV S RXMQ10ARY1
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Страница 349: ...SiAF332111E Check Part 6 Service Diagnosis 343 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 366: ...SiAF332111E 360 Part 7 Appendix 1 Wiring Diagrams 361 1 1 Outdoor Unit 361 1 2 VRV Indoor Unit 366 Part 7 Appendix...
Страница 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Страница 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Страница 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Страница 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 376: ...Wiring Diagrams SiAF332111E 370 Part 7 Appendix 1 2 4 Wall Mounted FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...