Field Settings for Outdoor Unit (10/12 HP Models)
SiAF332111E
156
Part 5 Field Settings and Test Operation
4.2.2 Mode 1
Mode 1 can be used to monitor the current situation of the outdoor unit. Some field setting
contents can be monitored as well.
Below the settings in mode 1 are explained.
[1-0]:
shows whether the unit you check is a master, slave 1 or slave 2 unit.
No indication: undefined situation
0: outdoor unit is master unit
1: outdoor unit is slave 1 unit
2: outdoor unit is slave 2 unit
Master, slave 1 and slave 2 indications are relevant in multiple outdoor unit
system configurations. The allocation of which outdoor unit is master, slave 1
or slave 2 are decided by the unit’s logic.
The master unit should be used to input field settings in mode 2.
[1-1]:
shows the status of low night noise operation.
1: unit is currently operating under low noise restrictions
0: unit is currently not operating under low noise restrictions
Night-time low noise operation reduces the sound generated by the unit
compared to nominal operating conditions.
Night-time low noise operation can be set in mode 2. There are two methods
to activate night-time low noise operation of the outdoor unit system.
The first method is to enable an automatic night-time low noise operation
during night time by field setting. The unit will operate at the selected low
noise level during the selected time frames.
The second method is to enable night-time low noise operation based on an
external input. For this operation an optional accessory is required.
[1-2]:
shows the status of power consumption limitation operation.
1: unit is currently operating under power consumption limitation
0: unit is currently not operating under power consumption limitations
Power consumption limitation reduces the power consumption of the unit
compared to nominal operating conditions.
Power consumption limitation can be set in mode 2.
There are two methods to activate power consumption limitation of the
outdoor unit system.
The first method is to enable a forced power consumption limitation by field
setting. The unit will always operate at the selected power consumption
limitation.
The second method is to enable power consumption limitation based on an
external input. For this operation an optional accessory is required.
[1-5]:
shows the current Te target parameter position.
[1-10]:
shows the total number of connected indoor units.
It can be convenient to check if the total number of indoor units which are
installed match the total number of indoor units which are recognized by the
system. In case there is a mismatch, it is advised to check the
communication wiring path between outdoor and indoor units (F1/F2
communication line).
Содержание VRV S RXMQ10ARY1
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Страница 349: ...SiAF332111E Check Part 6 Service Diagnosis 343 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 366: ...SiAF332111E 360 Part 7 Appendix 1 Wiring Diagrams 361 1 1 Outdoor Unit 361 1 2 VRV Indoor Unit 366 Part 7 Appendix...
Страница 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Страница 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Страница 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Страница 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 376: ...Wiring Diagrams SiAF332111E 370 Part 7 Appendix 1 2 4 Wall Mounted FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...