Field Settings for Outdoor Unit (10/12 HP Models)
Part 5 Field Settings and Test Operation
159
[2-30]:
Power consumption limitation level (step 1) via the external control adaptor
(DTA104A61/62)
If the system needs to be running under power consumption limitation conditions
when an external signal is sent to the unit, this setting defines the level power
consumption limitation that will be applied for step 1. The level is according to the
table.
Value
[2-30]
Power consumption limitation
1
60%
2
65%
3
70% (default)
4
75%
5
80%
6
85%
7
90%
8
95%
[2-31]:
Power consumption limitation level (step 2) via the external control adaptor
(DTA104A61/62)
If the system needs to be running under power consumption limitation conditions
when an external signal is sent to the unit, this setting defines the level power
consumption limitation that will be applied for step 2. The level is according to the
table.
Value
[2-31]
Power consumption limitation
1
40% (default)
2
50%
3
55%
[2-32]:
Forced, all time, power consumption limitation operation (no external control adaptor
is required to perform power consumption limitation)
If the system always needs to be running under power consumption limitation
conditions, this setting activates and defines the level power consumption limitation
that will be applied continuously. The level is according to the table.
Value
[2-32]
Restriction reference
0
Function not active (default)
1
Follows [2-30] setting
2
Follows [2-31] setting
[2-35]:
Height difference setting
Default value: 1
In case the outdoor unit is installed in the lowest position (indoor units are installed
on a higher position than outdoor units) and the height difference between the
highest indoor unit and the outdoor unit exceeds 40 m (131 ft), the setting [2-35]
should be changed to 0.
[2-45]:
Technical cooling
Value
[2-45]
Description
0
No technical cooling available (default)
1
Technical cooling available
Содержание VRV S RXMQ10ARY1
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Страница 349: ...SiAF332111E Check Part 6 Service Diagnosis 343 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 366: ...SiAF332111E 360 Part 7 Appendix 1 Wiring Diagrams 361 1 1 Outdoor Unit 361 1 2 VRV Indoor Unit 366 Part 7 Appendix...
Страница 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Страница 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Страница 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Страница 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 376: ...Wiring Diagrams SiAF332111E 370 Part 7 Appendix 1 2 4 Wall Mounted FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...