Field Settings for Outdoor Unit (6/8 HP Models)
SiAF332111E
134
Part 5 Field Settings and Test Operation
Setting does not return to factory setting when exit mode 2. To cancel the function, change
setting manually to factory setting.
Once function is activated
t01
appears. To stop current function, press once BS3 “Return”
button.
For detailed description about each setting, refer to
Details of Setting Mode (Mode 2)
on page
135.
Indication
bold
means factory setting.
No.
Item
Contents
Description
Display
Description
Display
SEG
1
SEG
2
SEG
3
SEG
1
SEG
2
SEG
3
29
Capacity priority Cancel the low noise level control if
capacity is required while low noise
operation or night-time low noise
operation is in progress.
2.
2
9
OFF
ON
0
1
30
Demand 1
setting
Used to make a change to the targeted
power consumption level when the
demand 1 control signal is inputted.
2.
3
0
Level 1 (60%)
Level 2 (65%)
Level 3 (70%)
Level 4 (75%)
Level 5 (80%)
Level 6 (85%)
Level 7 (90%)
Level 8 (95%)
1
2
3
4
5
6
7
8
31
Demand 2
setting
Used to use a targeted power current
level when the demand 2 control signal
is inputted.
2.
3
1
Level 1 (40%)
Level 2 (50%)
Level 3 (55%)
1
2
3
32
Constant
demand setting
Used to set constant demand 1 or 2
control without inputting any external
signal.
2.
3
2
OFF
Demand 1 (Mode 2-30)
Demand 2 (Mode 2-31)
0
1
2
34
Indoor fan upper
limit
Forced fan speed to low indoor units
thermostat ON if total indoor
thermostat-ON > index 130.
2.
3
4
Cooling and heating
Heating only
Never
0
1
2
35
Tc target setting To change Tc target cooling.
2.
3
5
Higher
Lower
Do not use
0
1
~7
42
Outdoor fan
Outdoor fan noise countermeasure (limit
fan speed).
2.
4
2
Standard
Mode A
Mode B
0
1
2
76
VRTsmart
control
Te upper limit
Used to change upper limit of target
evaporation temperature in VRTsmart
control.
2.
7
6
Low 1
Low 2
Low 3
Low 4
Low 5
Low 6
Standard
High
0
1
2
3
4
5
6
7
78
VRT control
Te upper limit
Used to change upper limit of target
evaporation temperature in VRT control.
2.
7
8
Standard
High
4
6
81
Cooling comfort setting
2.
8
1
ECO
Mild
Quick
Powerful
0
1
2
3
83 Master remote control setting when mix combination
2.
8
3
VRV
indoor
RA indoor
—
—
0
1
90
Indoor unit
without power
Possible for operate system when some
indoor units are temporary without
power supply.
2.
9
0
Disabled
Enabled
0
1
95
Eco level setting for VRTsmart
2.
9
5
Standard
Middle
High
0
1
2
96
Eco level setting for Eco mode by main PCB
2.
9
6
OFF
Low
Standard
0
1
2
Содержание VRV S RXMQ10ARY1
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Страница 349: ...SiAF332111E Check Part 6 Service Diagnosis 343 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 366: ...SiAF332111E 360 Part 7 Appendix 1 Wiring Diagrams 361 1 1 Outdoor Unit 361 1 2 VRV Indoor Unit 366 Part 7 Appendix...
Страница 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Страница 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Страница 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Страница 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 376: ...Wiring Diagrams SiAF332111E 370 Part 7 Appendix 1 2 4 Wall Mounted FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...