Field Settings for Outdoor Unit (6/8 HP Models)
Part 5 Field Settings and Test Operation
145
Image of operation in the case of A
Image of operation in the case of B
Image of operation in the case of A and B
Operation
sound
Rated
Level 1
Level 2
Level 3
The power consumption may
be decreased by about 10%.
The power consumption may
be decreased by about 20%.
The power consumption may
be decreased by about 30%.
Note 1: Above values are reference only (measured in silent room)
Note 2: Target sound level
Operation sound level set with External low noise setting
If capacity priority is set in
Capacity priority setting, the fan
speed will be increased according
to the load of air conditioning
when load is heavier.
Operation sound
during low noise
mode can be set with
External low noise
level setting (Factory
setting is level 2.)
Low noise mode instructing
Level 1
Level 2
Level 3
6 HP
50 dB
45 dB
40 dB
8 HP
55 dB
50 dB
45 dB
Operation
so
u
nd
Rated
Le
v
el 1
Le
v
el 2
Le
v
el 3
Time set
w
ith night-time lo
w
noise
operation start setting
If capacity priority is set in
Capacity priority setting, the fan
speed
w
ill
b
e increased
according to the load of air
conditioning
w
hen load is hea
v
ier.
Time set
w
ith night-time lo
w
noise operation end setting
Operation so
u
nd d
u
ring
night-time lo
w
noise
operation mode can
b
e set
w
ith night-time lo
w
noise
operation le
v
el setting.
(Factory setting is OFF.)
N
ight-time
Operation so
u
nd le
v
el set
w
ith
night-time lo
w
noise operation
setting
6:00 AM
8
:00 PM 10:00 PM 12:00 AM
7:00 AM
8
:00 AM
Set
w
ith night-time lo
w
noise operation end setting.
(Factory setting is
8
:00 AM.)
Set
w
ith night-time lo
w
noise operation start setting.
(Factory setting is 10:00 PM.)
Operation
sound
Rated
Level 1
Level 2
Level 3
Time set with night-time low noise
operation start setting
Low noise mode
instructing
Operation sound set with
External low noise setting
10:00 PM
8:00 PM
12:00 AM
6:00 AM 7:00 AM 8:00 AM
Set with night-time low noise operation start setting.
(Factory setting is 10:00 PM.)
Set with night-time low noise operation end setting.
(Factory setting is 8:00 AM.)
Low noise
mode instructing
Operation sound set with
External low noise setting
Night-time
If capacity priority is set in
Capacity priority setting, the fan
speed will be increased
according to the load of air
conditioning when load is heavier.
Time set with night-time low noise
operation end setting
Operation sound during
low noise mode can be set
with External quiet operation
level setting.
(Factory setting is level 2.)
Operation sound during
night-time low noise operation
mode can be set with night-time
low noise operation level setting.
(Factory setting is OFF.)
When external low noise
instruction is received during
the operation with night-time
low noise operation mode.
Level 2 precedes level 1 and
level 3 precedes level 2.
Operation sound level set
with night-time low noise
operation setting
Содержание VRV S RXMQ10ARY1
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Страница 349: ...SiAF332111E Check Part 6 Service Diagnosis 343 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 366: ...SiAF332111E 360 Part 7 Appendix 1 Wiring Diagrams 361 1 1 Outdoor Unit 361 1 2 VRV Indoor Unit 366 Part 7 Appendix...
Страница 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Страница 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Страница 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Страница 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 376: ...Wiring Diagrams SiAF332111E 370 Part 7 Appendix 1 2 4 Wall Mounted FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...