SiAF332111E
Troubleshooting by Error Code
Part 6 Service Diagnosis
287
Note(s)
Troubleshooting
Is supply
voltage imbalance over
certain value?
(
1,
3)
Correct the open phase of
power supply.
Open phase?
Is the imbalance of
voltage applied to the inverter
over certain value?
(
2,
3)
Rectify the power supply
voltage imbalance.
Take countermeasures (listed
below).
YES
YES
NO
NO
NO
Take countermeasures.
Defective noise filter, inverter
PCB or wiring
Turn OFF the power supply,
and then check and repair
wirings in the main circuit and
defective components.
(1) Loose contact and wiring
disconnection between the
power supply and the
inverter
(2) Wiring disconnection in or
loose contact of noise filter
Replace the inverter PCB
(A3P).
YES
Explanation to users
Use the document “Notice of Inspection Results” attached to spare part.
Hand the “Notice of Inspection Results” to user to ask
him/her to rectify the imbalance.
Be sure to explain user that “power supply
voltage imbalance” will occur and Daikin
accepts no responsibility for the imbalance.
Record the power supply voltage
between the three phases (L1-L2,
L2-L3, L3-L1) continuously for about
one week using a memory recorder
that can constantly record the voltage.
Power supply voltage imbalance Even
though power supply voltage remains
balanced when making measurement,
it often becomes imbalanced during
nighttime (from 06:00 PM to 10:00 PM).
Even though the power
supply voltage is normal, the
error recurs.
<If voltage can be monitored>
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
1. Make measurement of voltage at the power supply terminal block (X1M).
2. Make measurement of voltage at the L1, L2 and L3 terminals of diode module located on
the inverter PCB during the compressor is in operation.
3. RXMQ8AR: approximately 12 V
RXMQ10/12AR: approximately 6 V
Содержание VRV S RXMQ10ARY1
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Страница 349: ...SiAF332111E Check Part 6 Service Diagnosis 343 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 366: ...SiAF332111E 360 Part 7 Appendix 1 Wiring Diagrams 361 1 1 Outdoor Unit 361 1 2 VRV Indoor Unit 366 Part 7 Appendix...
Страница 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Страница 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Страница 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Страница 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 376: ...Wiring Diagrams SiAF332111E 370 Part 7 Appendix 1 2 4 Wall Mounted FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...