SiAF332111E
Field Settings for Outdoor Unit (10/12 HP Models)
Part 5 Field Settings and Test Operation
157
4.2.3 Mode 2
Mode 2 is used to change the field settings of the system.
Consulting the current field setting value and changing the current field setting value is possible.
In general, normal operation can be resumed without special intervention after changing field
settings.
Some field settings are used for special operation (e.g., 1 time operation, recovery/vacuuming
setting, manual adding refrigerant setting, etc.). In such a case, it is required to abort the special
operation before normal operation can restart. It will be displayed in below explanations.
[1-13]:
shows the total number of connected outdoor units (in case of multiple outdoor
system).
It can be convenient to check if the total number of outdoor units which are installed
matches the total number of outdoor units which are recognized by the system. In
case there is a mismatch, it is advised to check the communication wiring path
between outdoor and outdoor units (Q1/Q2 communication line).
[1-17]:
shows the latest error code.
[1-18]:
shows the error code which occurred 1 time before current error code.
[1-19]:
shows the error code which occurred 2 time before current error code.
When the latest error codes were reset by accident on an indoor unit user interface,
they can be checked again through this monitoring settings. Detailed information
about error codes can be consulted in the service manual of this unit.
[1-40]:
shows the current cooling comfort setting.
[2-8]:
Te target temperature during cooling operation
Value
[2-8]
Te target
0
Auto (default)
2
6°C
3
7°C
4
8°C
5
9°C
6
10°C
7
11°C
[2-12]:
Enable the low night noise function and/or power consumption limitation via external
control adaptor (DTA104A61/62)
If the system needs to be running under night-time low noise operation or under
power consumption limitation conditions when an external signal is sent to the unit,
this setting should be changed. This setting will only be effective when the optional
external control adaptor (DTA104A61/62) is installed.
Default value: 0
To activate this function: 1
[2-18]:
Fan high static pressure setting
In order to increase the static pressure the outdoor fan is delivering, this setting
should be activated.
For details about this setting, see technical specifications.
Default value: 0
To activate this function: 1
Содержание VRV S RXMQ10ARY1
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Страница 349: ...SiAF332111E Check Part 6 Service Diagnosis 343 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 366: ...SiAF332111E 360 Part 7 Appendix 1 Wiring Diagrams 361 1 1 Outdoor Unit 361 1 2 VRV Indoor Unit 366 Part 7 Appendix...
Страница 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Страница 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Страница 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Страница 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 376: ...Wiring Diagrams SiAF332111E 370 Part 7 Appendix 1 2 4 Wall Mounted FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...