Troubleshooting by Error Code
SiAF332111E
252
Part 6 Service Diagnosis
Reference
Reference
5.31.3 Discharge Pipe Temperature Abnormality (10/12 HP Models)
Applicable
Models
RXMQ10/12AR
Error Code
F3
Method of Error
Detection
Abnormality is detected according to the temperature detected with the discharge pipe or
compressor body thermistor.
Error Decision
Conditions
When discharge pipe temperature becomes abnormally high (135°C or more)
When discharge pipe temperature rises sharply (remains at 120°C or more for a continuous
period of 10 minutes)
When compressor body temperature becomes abnormally high (120°C or more)
When compressor body temperature rises sharply (remains at 110°C or more for a continuous
period of 10 minutes)
Supposed
Causes
Abnormal discharge pipe temperature
Defective discharge pipe thermistor
Abnormal compressor body temperature
Defective compressor body thermistor
Defective outdoor unit main PCB
Troubleshooting
1: Use a surface thermistor to measure the actual temperature.
Refer to
CHECK 11
for temperature and resistance properties of the thermistor.
CHECK 3
Refer to page 339.
CHECK 11
Refer to page 350.
NO
NO
Replace the relevant
thermistor.
Replace the outdoor
unit main PCB (A1P).
Connect the Service Checker.
Reset system operation, and then restart operation.
YES
YES
- All thermistors are normal, and temperature detection with the
outdoor unit main PCB is also normal.
- The discharge pipe actual temperature (or compressor body
temperature) rises.
CHECK 3
Eliminate the causes of superheating operation.
Service Checker
Connect the service checker to compare the discharge pipe temperature
(or compressor body temperature) and the actual measured value of the
discharge pipe surface temperature (or compressor body temperature) (
1).
Is the
temperature checked by the
service checker the same as the actual
measured value of the
temperature?
Are the
characteristics of the
discharge pipe and compressor body
thermistors normal?
CHECK 11
Содержание VRV S RXMQ10ARY1
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Страница 349: ...SiAF332111E Check Part 6 Service Diagnosis 343 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 366: ...SiAF332111E 360 Part 7 Appendix 1 Wiring Diagrams 361 1 1 Outdoor Unit 361 1 2 VRV Indoor Unit 366 Part 7 Appendix...
Страница 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Страница 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Страница 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Страница 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 376: ...Wiring Diagrams SiAF332111E 370 Part 7 Appendix 1 2 4 Wall Mounted FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...