Field Setting from Outdoor Unit
SiUS341802EC
185
Part 5 Field Settings and Test Operation
[2-26]:
Night-time low noise operation start time
Change [2-26] to 1, 2 or 3 in function of required timing.
Default value: 2
Value
[2-26]
Start time automatic night-time low noise
operation (approximately)
1
About 8:00 PM
2 (default)
About 10:00 PM
3
About 12:00 AM
This setting is used in conjunction with setting [2-22].
[2-27]:
Night-time low noise operation stop time
Default value: 3
Value
[2-27]
Stop time automatic night-time low noise
operation (approximately)
1
About 6:00 AM
2
About 7:00 AM
3 (default)
About 8:00 AM
This setting is used in conjunction with setting [2-22].
[2-28]:
Power transistor check mode
To evaluate the output of the power transistors. Use this function in case error code is
displayed related to defective inverter PCB or compressor is locked.
Default value: 0. Power transistor check mode is not active.
Field setting 1: Power transistor check mode is active.
Function:
Inverter PCB gives output of 10 Hz in sequence by all 6 transistors. Remove the
U/V/W terminals of the compressor, and connect to the inverter checker module. If all 6
LEDs blink, the transistors switch correctly.
When the power transistor check mode is interrupted, after internal power circuit is
disconnected on the inverter PCB, 2 LEDs will light up to indicate discharge of the DC
voltage. Wait till the LEDs are OFF before returning fasten terminals back to the
compressor terminals.
Minimum requirements to refer to the result on the inverter checker module:
All 3 phases and neutral are available, and
Inverter PCB control is active. Check if the green LED HAP on the inverter PCBs are
blinking normal (approx. 1/second). If LEDs are OFF, need to exit the standby mode of
the inverter:
Disconnect and reconnect power supply control PCB, or
Forced thermostat ON condition, or
Briefly set 2-6-1 (forced thermostat ON indoor), or 2-20-1 (manual refrigerant charge).
Once the LED is blinking on the inverter PCB, change related setting immediately
back to set 0 to deactivate related function.
Diode module generates the required 260 VDC for RXLQ-TATJ* and RXLQ-TBTJ*,
600 VDC for RXLQ-TAYD* and RXLQ-TBYD*, or 750 VDC for RXLQ-TAYC*,
RXLQ-TBYC*, and RXYQ-TAYC*.
Содержание VRV Aurora RXLQ-TATJU Series
Страница 376: ...Check SiUS341802EC 369 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 378 CHECK 8 Refer to page 379...
Страница 405: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 398 1 Wiring Diagrams 1 1 Outdoor Unit RXLQ72TATJU RXLQ72TATJA 2D112580C...
Страница 407: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 400 RXLQ96 120TATJU RXLQ96 120TATJA 2D112581C...
Страница 409: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 402 RXLQ72TAYDU RXLQ72TAYDA 2D112582D...
Страница 411: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 404 RXLQ96 120TAYDU RXLQ96 120TAYDA 2D112583D...
Страница 417: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 410 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 418: ...Wiring Diagrams SiUS341802EC 411 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ T 3D076375A...
Страница 420: ...Wiring Diagrams SiUS341802EC 413 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 425: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 418 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 426: ...Wiring Diagrams SiUS341802EC 419 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 427: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 420 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 429: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 422 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 433: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 426 FXHQ12 24 36MVJU 3D048116C...
Страница 434: ...Wiring Diagrams SiUS341802EC 427 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 441: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 434 VAM1200GVJU 3D073270D...