Field Setting from Outdoor Unit
SiUS341802EC
191
Part 5 Field Settings and Test Operation
[2-38]:
Emergency operation “Master”
To disable permanent compressor operation: in case of single module or “Master”
unit of a multi outdoor system, this setting allows:
Default value: 0. Compressor operation enabled.
Field setting:
Set 1 or 3: compressor in this "Master" module is disabled permanently.
[2-39]:
Emergency operation “Slave 1”
To disable permanent compressor operation of “Slave 1” unit of a multi outdoor
system (RXYQ-TA):
Default value: 0. Compressor operation enabled.
Field setting:
Set 1 or 3: compressor in this "Slave 1" module is disabled permanently.
[2-40]:
Emergency operation “Slave 2”
To disable permanent compressor operation of “Slave 2” unit of a multi outdoor
system (RXYQ-TA):
Default value: 0. Compressor operation enabled.
Field setting:
Set 1 or 3: compressor in this "Slave 2" module is disabled permanently.
Combination table setting 2-38, 2-39 and 2-40:
Disable
Master/individual
Slave 1
Slave 2
Module
2-38-1 or 2-38-3
2-39-1 or 2-39-3
2-40-1 or 2-40-3
[2-42]:
Outdoor fan noise countermeasure
Change fans rotational speed and reduce noise by the interference of air blow noise
between outdoor units.
Default value: 0
Field setting:
Mode A: 1
Mode B: 2
[2-49]:
Height difference setting
Default value: 0.
In case the outdoor unit is installed in the highest position (indoor units are installed
on a lower position than outdoor units) and the height difference between the lowest
indoor unit and the outdoor unit exceeds 50 m (164 ft), the setting [2-49] has to be
changed to 1.
[2-51]:
Master/Slave setting Multi
When 2 or 3 modules are installed as a multi-outdoor (by common refrigerant piping
and wiring by terminals Q1Q2) configuration is automatically detected. In certain
cases, the sequence of the slave units need to be set manually (in case of AIRNET
monitoring).
Default value: 0. Automatic detection.
Field setting: ensure that the modules in a multi are set different status. Even some
modules in a multi are set manually to same status, U7 error will appear.
1: forced “Master” (F1F2/Ind terminals should be connected to indoor units).
2: forced “Slave 1” (only Q1Q2 terminals should be wired to “Master” module).
3: forced “Slave 2” (only Q1Q2 terminals should be wired to “Master” module).
Содержание VRV Aurora RXLQ-TATJU Series
Страница 376: ...Check SiUS341802EC 369 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 378 CHECK 8 Refer to page 379...
Страница 405: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 398 1 Wiring Diagrams 1 1 Outdoor Unit RXLQ72TATJU RXLQ72TATJA 2D112580C...
Страница 407: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 400 RXLQ96 120TATJU RXLQ96 120TATJA 2D112581C...
Страница 409: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 402 RXLQ72TAYDU RXLQ72TAYDA 2D112582D...
Страница 411: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 404 RXLQ96 120TAYDU RXLQ96 120TAYDA 2D112583D...
Страница 417: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 410 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 418: ...Wiring Diagrams SiUS341802EC 411 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ T 3D076375A...
Страница 420: ...Wiring Diagrams SiUS341802EC 413 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 425: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 418 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 426: ...Wiring Diagrams SiUS341802EC 419 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 427: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 420 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 429: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 422 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 433: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 426 FXHQ12 24 36MVJU 3D048116C...
Страница 434: ...Wiring Diagrams SiUS341802EC 427 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 441: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 434 VAM1200GVJU 3D073270D...