SiUS341802EC
Field Setting from Outdoor Unit
Part 5 Field Settings and Test Operation
192
Note(s)
This setting may result in a longer reaction time to large load variations.
[2-60]:
Gas furnace setting
Default value: 0.
When a gas furnace is connected, the setting [2-60] has to be changed to 1.
[2-62]:
Cooling and heating capacity learning control
Default value: 0.
Value
[2-62]
Description
0 (default)
OFF
1
Cooling adjustment
2
Heating adjustment
3
Cooling and heating adjustment
Adjust cooling and heating system operation to achieve stable capacity.
[2-78]:
Heat pump lockout temperature
Heat pump is locked out when the outdoor ambient temperature is smaller than the
heat pump lockout temperature.
This is only effective when the heat pump lockout 2 setting [2-37] is Mode 3 to 6.
Value
[2-78]
Heat pump lockout temperature
0 (default)
–26.1°C (–15°F)
1
–23.3°C (–10°F)
2
–20.5°C (–5°F)
3
–17.7°C (0°F)
4
–15°C (5°F)
5
–12.2°C (10°F)
6
–9.4°C (15°F)
7
–6.6°C (20°F)
8
–3.8°C (25°F)
9
–1.1°C (30°F)
10
1.6°C (35°F)
11
4.4°C (40°F)
12
7.2°C (45°F)
13
10°C (50°F)
14
Forced heat pump lockout
[2-79]:
Heat pump lockout release differential
Heat pump is resumed when the outdoor ambient temperature is recovered by
differential above the heat pump lockout temperature.
Value
[2-79]
Heat pump lockout release differential
0
2.8°C (5°F)
1 (default)
5.6°C (10°F)
2
8.3°C (15°F)
Содержание VRV Aurora RXLQ-TATJU Series
Страница 376: ...Check SiUS341802EC 369 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 378 CHECK 8 Refer to page 379...
Страница 405: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 398 1 Wiring Diagrams 1 1 Outdoor Unit RXLQ72TATJU RXLQ72TATJA 2D112580C...
Страница 407: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 400 RXLQ96 120TATJU RXLQ96 120TATJA 2D112581C...
Страница 409: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 402 RXLQ72TAYDU RXLQ72TAYDA 2D112582D...
Страница 411: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 404 RXLQ96 120TAYDU RXLQ96 120TAYDA 2D112583D...
Страница 417: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 410 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 418: ...Wiring Diagrams SiUS341802EC 411 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ T 3D076375A...
Страница 420: ...Wiring Diagrams SiUS341802EC 413 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 425: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 418 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 426: ...Wiring Diagrams SiUS341802EC 419 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 427: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 420 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 429: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 422 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 433: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 426 FXHQ12 24 36MVJU 3D048116C...
Страница 434: ...Wiring Diagrams SiUS341802EC 427 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 441: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 434 VAM1200GVJU 3D073270D...