SiUS341802EC
Troubleshooting by Error Code
Part 6 Service Diagnosis
228
U2 - 01
Shortage of inverter 1 power supply voltage (Master)
Make a diagnosis of the relevant unit based on the
following.
Shortage of power supply voltage
If the other units detect shortage of power supply voltage,
power supply voltage during operation may be unstable.
Check the power supply condition.
If a particular unit detects the error, operation of 52C may
be defective. Follow the
U2
flowchart.
Open phase of power supply
The wiring between power supply and inverter PCB may be
disconnected. Check that power supply is connected to
terminal block, terminal block is connected to PCB without
broken wire or disconnection, and reactor wiring is
secured. If no abnormality is found, follow the
U2
flowchart.
Defective capacitor in main circuit
P-N on the inverter PCB (electrolytic capacitor, power
module) may be damaged and short circuited. Operation of
current limiting relay may be defective or the wiring
between the reactor and PCB may be disconnected.
Measure the resistance between P-N on the inverter PCB
and check for short circuit. If no abnormality is found, follow
the
U2
flowchart.
U2 - 02
Open phase of inverter 1 power supply (Master)
U2 - 03
Defective capacitor in inverter 1 main circuit (Master)
U2 - 08
Shortage of inverter 1 power supply voltage (Slave 1)
U2 - 09
Open phase of inverter 1 power supply (Slave 1)
U2 - 10
Defective capacitor in inverter 1 main circuit (Slave 1)
U2 - 11
Shortage of inverter 1 power supply voltage (Slave 2)
U2 - 12
Open phase of inverter 1 power supply (Slave 2)
U2 - 13
Defective capacitor in inverter 1 main circuit (Slave 2)
U2 - 36
Fan motor 1 undervoltage (Master)
U2 - 37
Fan motor 2 undervoltage (Master)
U2 - 38
Fan motor 1 undervoltage (Slave 1)
U2 - 39
Fan motor 2 undervoltage (Slave 1)
U2 - 40
Fan motor 1 undervoltage (Slave 2)
U2 - 41
Fan motor 2 undervoltage (Slave 2)
U3 - 02
Initial installation warning
Refer to the
U3
flowchart and make a diagnosis of the
relevant unit based on the Error code shown to the left.
U3 - 03
Test operation not conducted
U3 - 04
Abnormal end of test operation
U3 - 05
Premature end of test operation during initial transmission
error
U3 - 06
Premature end of test operation during normal
transmission error
U3 - 07
Premature end of test operation due to transmission error
of either unit
U3 - 08
Premature end of test operation due to transmission error
of all units
U4 - 01
Transmission error between indoor units and outdoor units Refer to the
U4
flowchart and make a diagnosis of the
relevant unit based on the Error code shown to the left.
U4 - 03
Transmission error between indoor unit and system
U7 - 01
Error when external control adaptor for outdoor unit is
installed
Refer to the
U7
flowchart and make a diagnosis of the
relevant unit based on the Error code shown to the left.
U7 - 02
Warning when external control adaptor for outdoor unit is
installed
U7 - 03
Transmission error between master and slave 1 units
U7 - 04
Transmission error between master and slave 2 units
U7 - 05
Multi system error
U7 - 06
Error in address settings of slave 1 and 2
U7 - 07
Connection of four or more outdoor units in the same
system
U7 - 11
Error in indoor unit connection capacity for test operation
U9 - 01
Other indoor units abnormality
Refer to the
U9
flowchart and make a diagnosis of the
relevant unit based on the Error code shown to the left.
UA - 13
Refrigerant type error
The type of refrigerant used for the indoor unit is different
from that used for the outdoor unit.
UA - 15
Not applicable for self-cleaning decoration panel
[when the self-cleaning decoration panel is mounted]
An outdoor unit is not applicable for the self-cleaning
decoration panel is connected.
Error code
Troubleshooting
Error Description
Diagnosis
Содержание VRV Aurora RXLQ-TATJU Series
Страница 376: ...Check SiUS341802EC 369 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 378 CHECK 8 Refer to page 379...
Страница 405: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 398 1 Wiring Diagrams 1 1 Outdoor Unit RXLQ72TATJU RXLQ72TATJA 2D112580C...
Страница 407: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 400 RXLQ96 120TATJU RXLQ96 120TATJA 2D112581C...
Страница 409: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 402 RXLQ72TAYDU RXLQ72TAYDA 2D112582D...
Страница 411: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 404 RXLQ96 120TAYDU RXLQ96 120TAYDA 2D112583D...
Страница 417: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 410 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 418: ...Wiring Diagrams SiUS341802EC 411 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ T 3D076375A...
Страница 420: ...Wiring Diagrams SiUS341802EC 413 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 425: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 418 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 426: ...Wiring Diagrams SiUS341802EC 419 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 427: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 420 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 429: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 422 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 433: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 426 FXHQ12 24 36MVJU 3D048116C...
Страница 434: ...Wiring Diagrams SiUS341802EC 427 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 441: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 434 VAM1200GVJU 3D073270D...