SiUS341802EC
Field Setting from Outdoor Unit
Part 5 Field Settings and Test Operation
202
In case of heating operation the condense temperature is allowed to go up to 115°F (46°C) on
temporary base depending on the situation.
When the request from the indoor units becomes more moderate, the system will eventually go to
the steady state condition which is defined by the operation method above.
To activate the quick comfort setting under cooling operation, change field setting [2-81] to 2.
This setting is used in conjunction with settings [2-8].
To activate the quick comfort setting under heating operation, change field setting [2-82] to 2.
This setting is used in conjunction with setting [2-9].
• Mild
Overshoot (during heating operation) or undershoot (during cooling operation) is allowed compared
to the requested refrigerant temperature, in order to achieve the required room temperature very
fast. The overshoot is not allowed from the start up moment. The start up occurs under the
condition which is defined by the operation mode above.
In case of cooling operation the evaporating temperature is allowed to go down to 43°F (6°C) on
temporary base depending on the situation.
In case of heating operation the condense temperature is allowed to go up to 115°F (46°C) on
temporary base depending on the situation.
When the request from the indoor units becomes more moderate, the system will eventually go to
the steady state condition which is defined by the operation method above.
The start up condition is different from the powerful and quick comfort setting.
To activate the mild comfort setting under cooling operation, change field setting [2-81] to 1.
This setting is used in conjunction with settings [2-8].
To activate the mild comfort setting under heating operation, change field setting [2-82] to 1.
This setting is used in conjunction with setting [2-9].
• Eco
The original refrigerant temperature target, which is defined by the operation method (see above) is
kept without any correction, unless for protection control.
To activate the eco comfort setting under cooling operation, change field setting [2-81] to 0. This
setting is used in conjunction with setting [2-8].
To activate the eco comfort setting under heating operation, change field setting [2-82] to 0. This
setting is used in conjunction with setting [2-9].
No matter which control is selected, variations on the behavior of the system are still possible due
to protection controls to keep the unit operating under reliable conditions. The intentional target,
however, is fixed and will used to obtain the best balance between energy consumption and
comfort, depending on the application type.
Содержание VRV Aurora RXLQ-TATJU Series
Страница 376: ...Check SiUS341802EC 369 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 378 CHECK 8 Refer to page 379...
Страница 405: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 398 1 Wiring Diagrams 1 1 Outdoor Unit RXLQ72TATJU RXLQ72TATJA 2D112580C...
Страница 407: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 400 RXLQ96 120TATJU RXLQ96 120TATJA 2D112581C...
Страница 409: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 402 RXLQ72TAYDU RXLQ72TAYDA 2D112582D...
Страница 411: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 404 RXLQ96 120TAYDU RXLQ96 120TAYDA 2D112583D...
Страница 417: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 410 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 418: ...Wiring Diagrams SiUS341802EC 411 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ T 3D076375A...
Страница 420: ...Wiring Diagrams SiUS341802EC 413 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 425: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 418 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 426: ...Wiring Diagrams SiUS341802EC 419 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 427: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 420 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 429: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 422 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 433: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 426 FXHQ12 24 36MVJU 3D048116C...
Страница 434: ...Wiring Diagrams SiUS341802EC 427 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 441: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 434 VAM1200GVJU 3D073270D...