SiUS341802EC
Basic Control
Part 4 Functions and Control
94
Note(s)
5.4 Compressor Step Control
1. Depending on the operating conditions of compressors, the compressors may run in patterns
other than those aforementioned.
Compressor operations vary with the following steps according to information in Compressor PI Control on page 92.
Furthermore, the operating priority of compressors is subject to information in Operating Priority and Rotation of
Compressors on page 92.
Single unit installation
RXLQ72TA, RXLQ72TB
RXYQ72-120TA
Step No.
rps
Step No.
rps
Step No.
rps
1
15.0
61
36.7
121
84.5
2
15.2
62
37.2
122
85.7
3
15.4
63
37.7
123
86.9
4
15.6
64
38.3
124
88.1
5
15.9
65
38.8
125
89.4
6
16.2
66
39.3
126
90.6
7
16.5
67
39.9
127
91.9
8
16.8
68
40.5
128
93.2
9
17.1
69
41.0
129
94.5
10
17.4
70
41.6
130
95.8
11
17.7
71
42.2
131
97.2
12
18.0
72
42.8
132
98.5
13
18.3
73
43.4
133
99.9
14
18.6
74
44.0
134
101.3
15
19.0
75
44.6
135
102.7
16
19.4
76
45.2
136
104.2
17
19.8
77
45.8
137
105.6
18
20.1
78
46.5
138
107.1
19
20.5
79
47.1
139
108.4
20
20.7
80
47.8
140
110.1
21
21.0
81
48.5
141
111.7
22
21.3
82
49.1
142
113.2
23
21.6
83
49.8
143
114.8
24
21.9
84
50.5
144
116.4
25
22.2
85
51.1
145
118.0
26
22.5
86
52.0
146
119.7
27
22.9
87
52.7
147
121.4
28
23.2
88
53.4
148
123.1
29
23.5
89
54.2
149
124.8
30
23.8
90
54.9
150
126.5
31
24.2
91
55.7
151
128.3
32
24.5
92
56.5
152
130.1
33
24.9
93
57.3
153
132.0
34
25.2
94
58.1
154
133.8
35
25.5
95
58.9
155
135.7
36
25.9
96
59.7
156
137.6
37
26.3
97
60.5
157
139.5
38
26.6
98
61.4
158
140.0
39
27.0
99
62.3
40
27.4
100
63.4
41
27.8
101
64.0
42
28.1
102
64.9
43
28.5
103
65.6
44
29.0
104
66.6
45
29.4
105
67.7
46
29.8
106
68.6
47
30.2
107
69.6
48
30.6
108
70.6
49
31.0
109
71.6
50
31.5
110
72.6
51
31.9
111
73.6
52
32.4
112
74.6
53
32.8
113
75.7
54
33.3
114
76.7
55
33.8
115
77.8
56
34.2
116
78.9
57
34.7
117
80.0
58
35.2
118
81.1
59
35.7
119
82.2
60
36.2
120
83.4
RXYQ72TA heating upper limit
RXYQ96TA heating upper limit
RXLQ72TA, RXLQ72TB, RXYQ120TA heating upper limit
RXLQ72TA, RXLQ72TB, RXYQ72TA cooling upper limit
RXYQ96TA cooling upper limit
RXYQ120TA cooling upper limit
Содержание VRV Aurora RXLQ-TATJU Series
Страница 376: ...Check SiUS341802EC 369 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 378 CHECK 8 Refer to page 379...
Страница 405: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 398 1 Wiring Diagrams 1 1 Outdoor Unit RXLQ72TATJU RXLQ72TATJA 2D112580C...
Страница 407: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 400 RXLQ96 120TATJU RXLQ96 120TATJA 2D112581C...
Страница 409: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 402 RXLQ72TAYDU RXLQ72TAYDA 2D112582D...
Страница 411: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 404 RXLQ96 120TAYDU RXLQ96 120TAYDA 2D112583D...
Страница 417: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 410 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 418: ...Wiring Diagrams SiUS341802EC 411 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ T 3D076375A...
Страница 420: ...Wiring Diagrams SiUS341802EC 413 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 425: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 418 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 426: ...Wiring Diagrams SiUS341802EC 419 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 427: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 420 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 429: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 422 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 433: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 426 FXHQ12 24 36MVJU 3D048116C...
Страница 434: ...Wiring Diagrams SiUS341802EC 427 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...