SiUS341802EC
Outline of Control (Indoor Unit)
Part 4 Functions and Control
112
will be conducted. If the evaporator inlet temperature is kept at more than 7°C (44.6°F) for a
consecutive period of 10 min., the freeze-up prevention operation will be reset.
6. Thermostat status
7. The following models have the drain pump as standard equipment
FXFQ-AA, FXFQ-T, FXFQ-P, FXZQ-TA, FXZQ-TB, FXZQ-M, FXUQ-P, FXUQ-PA, FXEQ-P,
FXDQ-M, FXSQ-TA, FXSQ-TB, FXMQ-PB, FXMQ-TB
8. Program dry display
No set temperature and airflow rate of the remote controller are displayed.
9. Thermostat status
Set temperature when operating the program dry mechanism.
10. Fan operation
By setting the remote controller to Fan, the fan will operate with thermostat OFF in set temperature
control operation mode.
11. Set wind direction
According to wind direction instruction from the remote controller, the wind direction is set to 100%
horizontal while in heating operation.
12. Fan
According to fan speed instruction from the remote controller, the fan is put into operation in LL
mode while in heating operation.
13. Wind direction
When the heating thermostat turns OFF, the wind direction will be set to 100% horizontal.
14. Hot start
After the start of heating operation or the end of defrost operation, the hot start control will terminate
if the temperature at the condenser outlet (indoor heat exchanger liquid pipe temperature) exceeds
34°C (93.2°F), or if Tc is above 52°C (125.6°F), or if 3 minutes have elapsed.
15. Thermostat status
16. Outlet air temperature drop protection
When the set temperature is below 24°C (75.2°F) or the electronic expansion valve opening is
small, the protection will be activated.
17.
Hu
indicates the Humidifier connected to the wiring modification adaptor.
It is not related to the Humidifier terminals on the PCB of FXTQ-TA, FXTQ-TB, or CXTQ-TA.
18. Only for CXTQ-TA.
Refer to
Gas Furnace Control (CXTQ-TA Models)
on page 132 for details.
OFF
ON
a
b
Set temperature
a = b = 1°C (1.8°F) or 0.5°C (0.9°F)
The values a and b depend on the field setting 12(22)-2.
Suction air temperature
b
a
–2°C (28.4°F)
–4°C (24.8°F)
Suction air temp.
Set temp.
b
a
(3)
(2)
(1)
Содержание VRV Aurora RXLQ-TATJU Series
Страница 376: ...Check SiUS341802EC 369 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 378 CHECK 8 Refer to page 379...
Страница 405: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 398 1 Wiring Diagrams 1 1 Outdoor Unit RXLQ72TATJU RXLQ72TATJA 2D112580C...
Страница 407: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 400 RXLQ96 120TATJU RXLQ96 120TATJA 2D112581C...
Страница 409: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 402 RXLQ72TAYDU RXLQ72TAYDA 2D112582D...
Страница 411: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 404 RXLQ96 120TAYDU RXLQ96 120TAYDA 2D112583D...
Страница 417: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 410 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 418: ...Wiring Diagrams SiUS341802EC 411 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ T 3D076375A...
Страница 420: ...Wiring Diagrams SiUS341802EC 413 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 425: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 418 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 426: ...Wiring Diagrams SiUS341802EC 419 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 427: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 420 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 429: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 422 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 433: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 426 FXHQ12 24 36MVJU 3D048116C...
Страница 434: ...Wiring Diagrams SiUS341802EC 427 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 441: ...SiUS341802EC Wiring Diagrams Part 7 Appendix 434 VAM1200GVJU 3D073270D...